background image

--16-- 

Pilot Lamps: 

 
 

"Battery Full" 

(Board battery fully charged,

 green

):

 

 

If it is on: 

Battery has been charged to 100 %, trickle charge U2, finished. 

 

If it is flashing: 

Main charging process is effected in the charging phase U1, indication of the charging state of 
75 % (lead), approx. 90 % (LiFePO4) (short flashing), gradual increase to 100 % (long flashing). 

 

Off: 

Main charging process is still being executed in the phase I. 

 

"Main Charge" 

(Main charging board battery, 

yellow

):

 

 

If it is on: 

Main charging process is effected in the charging phase I or U1

.

 

 

Off: 

Trickle charge U2. 

 

If it is flashing: 

1.  Battery temperature sensor is not connected with charging program LiFePO4!

 

2.  External overvoltage board battery > 15.50 V after 20 seconds, 

 

 

automatic reset after drop to the normal nominal voltage.

 

 

"Current"

 (Charging Current,

 red

):

 

 

 

The lighting intensity will be 

reduced or increased depending on the supplied charging 

current

.

 

 

"Board OUT"

  

(Board battery, 

yellow

)

 

If it is on: 

The board battery will be controlled and charged during operation. 

 

If it turns off shortly  
every 2 s:  

Only LiFePO4:  Battery temperature below 0 °C. The charging current can be reduced for 
battery protection for all modes of charging. If the battery is discharged, longer charging times. 

 

If it is flashing: 

Battery Protection: Battery overtemperature > 50 °C (depending on type), switchover to low 
safety charging voltage and half of the max. charging current. Automatic return, as soon as the 
temperature is 2 °C less. 

"Start IN"  

(Starter Battery, 

yellow

)

 

If it is on: 

Pilot lamp for the starter battery during operation. 

 

If it is flashing: 

The voltage of the starter battery is too low or too high (only with D+ control). 

 

Is flashing shortly  

 

every 2 sec.: 

During idle mode and external charging of the board battery (such as mains supply charger, 
solar) auxiliary charging for the starter battery is active to keep its starting capacity (only with 
switch position "B", see page 14). 

 

"Power"

 (Mains, 

red)

:

 

 

If it is on: 

The charging converter had been activated and is ready for operation. 

 

If it turns off shortly  

 

every 2 s: 

The power control of the charging converter has reduced the output capacity by more than 30 
% (starter battery discharge protection, starting capacity is maintained), since the voltage of the 
starter battery dropped below the adjusted value for "Reduction of the charging capacity" 
(table 4). 

 

The charging capacity will be increased automatically, as soon as the voltage exceeds the value 
"increase of the charging capacity". 

 

If it is flashing: 

1.  Disconnection by safety timer. Duration of the charging phase I was too long (15 hours)

 

 

due to too many consumers or defective battery (short circuit of the cells). 

 

 

Reset only by removal of the signal at "D+ / Kl.15" (engine, ignition off). 

 

2.  Internal unit failure (overheating), automatic reset after cooling down. 

 

Off: 

Charging converter in idle mode. 

 

All LEDs

 "Battery Full", "Main Charge", "Current", "Board OUT", "Start IN" and "Power" 

  

are flashing simultaneously: 

 

The positions of the upper 4 selector switches (charging program acid, gel, AGM, LiFePO4) are incorrect. For 
reasons of safety, the unit has switched-off. 

 

Set the desired charging program battery type "Board" (design, technology), from page 11. 

 

 

Содержание VCC 1212-50

Страница 1: ...s excel by their compact design low weight high frequency switch mode technology and powerfully dimensioned power components for safe operation Significantly improved energy balance of the board batte...

Страница 2: ...ng and fuses of the customer which are already existing in the vehicle Only suitable for VCC 1212 50 page 4 Suitable for combination with electroblock EBL EVS with the existing cabling of the customer...

Страница 3: ...cross sections and lengths of the cables Never mix up the voltage sensor cables for start Vs and Vs and board Vb and Vb Insert fuses near the battery for protection of the cables Reverse battery 12 V...

Страница 4: ...12 50 The cabling and the fuses for the electroblock EBL provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually limit the maximum cur...

Страница 5: ...50 70 90 with full capacity The cabling and the fuses for the electroblock EBL provided by the customer are further used For this purpose insert a switching relay 12 V 60 A order No 2202 into the cabl...

Страница 6: ...y suitable for VCC 1212 50 The cabling with the fuses and the cutoff relay provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually lim...

Страница 7: ...to tables 1 The further cabling to the batteries including different cross sections is to be done directly at the relay The 12 V current requirement of the inverter might be higher than the output ca...

Страница 8: ...ntioned maximum values for Cable Length BOARD are only used to approx 2 3 VCC 1212 50 Cable Cross section Cable Length START In case of insulated body Cable Length Batt Fuse 2 Cable Protection Cable L...

Страница 9: ...ay in case of temporarily very high consumer current rates If not used leave the terminal blank The rating of the output is max 1 A and it is protected with a thermal fuse which resets itself after re...

Страница 10: ...age rates of 20 C 25 C being recommended by the battery manufacturers LiFePO4 Batteries Installation The thermal contact of sensor and inside temperature of the battery should be well Thus it should b...

Страница 11: ...temperature equalization for batteries in lead technology 1 Lead Acid Switch Position U1 14 40 V U2 13 50 V 2 6 h Universal charging program for acid lead acid batteries acc to DIN 57 510 VDE 0510 for...

Страница 12: ...emperature control adapted to lithium batteries Observe the instructions of the battery manufacturer An operation of the unit at a LiFePO4 battery without BMS Battery Management System and without equ...

Страница 13: ...U1 14 20 V U2 13 60 V 0 5 h Adapted to Victron LFP BMS 12 8 TransWatt TH 12 xxx of the indicated capacity rates Operation of the battery only with own BMS and prescribed safety circuit 7 LiFePO4 14 4...

Страница 14: ...ging port for the starter battery is existing in the system the function auxiliary charging of the charging converter is not required and should be switched off A Switch position to the left A Auxilia...

Страница 15: ...inuous signal at D without running engine might discharge the starter battery Increase of the charging capacity 12 50 V Reduction of the charging capacity 12 20 V Switching off threshold 12 00 V 30 se...

Страница 16: ...ellow If it is on Pilot lamp for the starter battery during operation If it is flashing The voltage of the starter battery is too low or too high only with D control Is flashing shortly every 2 sec Du...

Страница 17: ...uch as in EBL EVS bridges the charging converter Check connection plan Operation with EBL EVS etc m The charging converter changes permanently between active and quiescent condition D must arrive dire...

Страница 18: ...ion phase After that automatic switching to the following phase U1 4 During the phase U1 LED Main Charge is lighting the battery voltage will be kept constant on a high level The green LED Battery Ful...

Страница 19: ...ree from condensation water Never use the unit in locations where the risk of gas or dust explosion exists Open air operation of the unit is not allowed Lay the cables in a way that damage is avoided...

Страница 20: ...Ah 100 460 620 Ah 150 600 800 Ah LiFePO4 Charging Programs Stored in the Memory 4 4 4 Safety Charging Voltage at Battery Overtemperature 12 80 V 12 80 V 12 80 V Input T T for Battery Temperature Sens...

Отзывы: