background image

--17-- 

Start-up and Function Test:

 

After connection and setting of the charging converter, the function can be tested: 
1.

 

Start the vehicle:  

-

 

The charging converter will be activated and starts with 3% of the maximum charging capacity. 

-

 

The LEDs "Power”, "Start IN”, "Board OUT” and "Main Charge" will be lighting, LED "Current” is lighting dimly. 

2.

 

Increase the speed of the vehicle to increase the voltage at the starter battery until it exceeds the adjusted value for 
the "increase of the charging capacity". 

-

 

The charging capacity will be increased and is raised to the maximum value or to the required value of the charging 
characteristic line, if the board battery is already full.  

-

 

The lighting intensity of the LED "Current" will be reduced or increased depending on the charging current. 

 

Tips: 

Unit does not start, the LED "Power" is not lighting: 

a.

 

Check the voltage at the activation input terminal "D+", > 8 V. 

b.

 

In case of pure voltage control, check the voltage rates directly at the terminals according to table 4. 

Full charging current is not reached: 

c.

 

Check the adjustment of the slide switches "OUT Limit" according to table 2. 

d.

 

Board battery is already charged: Turn on devices with high current draw. 

e.

 

If required, deactivate the function "IN Limit" shortly for reasons of testing: Both switches to position "right". 

f.

 

Start IN 

Sensor Cables ("VS-"/"VS+"), if used: Check connection, insulation, polarity. 

g.

 

Board OUT 

Sensor Cables ("VB-"/"VB+"), if used: Check connection, insulation, polarity. 

h.

 

Never mix up the sensor cables Start IN 

("VS-"/"VS+") and

 

Board OUT 

("VB-"/"VB+"),

 

otherwise the voltage control 

of the unit will be led astray: check. 

Full charging current is not reached, the LED "Start IN" is flashing: 

i.

 

Check the voltage at teIN Start: >11.5 V. Increase the engine speed, in order that the charging converter is able 
to regulate to a higher voltage. 

j.

 

Check cabling –Com, +OUT board and fuse I. Check cross-sections and lengths according to table 1. If used, check 
cables Vs- and Vs+, Vb- and Vb+, as well as stripped cable ends. Measure the voltage directly at the terminals/their 
screws. 

k.

 

Check the cIN Start, fuse 2, cross-sections and lengths (also "minus" connection to chassis, if required, cable 
"-Batt." from the starter to the board battery) according to table 1.  

l.

 

Concealed battery cutoff relay (such as in EBL, EVS) bridges the charging converter:  Check connection plan. 

Operation with EBL, EVS etc.: 
m.

 

The charging converter changes permanently between active and quiescent condition: "D+" must arrive directly from 
the vehicle, and not from the EBL. 

 

Function of the Power Control at Starter Battery and Generator: 

The charging converter is voltage-controlled or activated via the control input "D+". It will be deactivated automatically if 
the engine is switched-off. It starts with 3 % of its achievable charging capacity. 
The setting of the two slide switches "D+ / Vs and Low / High" (see tables 4, page 15) now affects the further load of the 
starter battery circuit supplying current to the charging converter. 
After the engine start, also the starter battery shall be charged immediately and its starting capacity shall be maintained. 
Therefore, the charging converter does not start charging the board battery, before the voltage value "increase of the 
charging capacity" of the starter battery is reached. 
The gradual increase of the charging capacity for the board battery by the charging converter will be effected, if the voltage 
value "increase of the charging capacity" of the starter battery is still reached and exceeded. 
In case of strong load on the starter circuit due to many large consumers and the starter battery’s voltage drops again 
below the value "reduction of the charging capacity", such as during engine idling, there will be a gradual reduction of the 
charging capacity for the board battery to relieve the starter circuit. But the minimum charging capacity will always be 
approx. 3 % of the achievable charging capacity. 
If the voltage drops below the "Switching off threshold" for 30 seconds, the charging converter will be switched-off 
automatically. As soon as the voltage exceeds the threshold "increase of the charging capacity", the converter will be 
switched-on, and the capacity will be increased gradually until the required (maximum) charging capacity is reached. 
A reduction of the charging capacity by more than 30 % due to insufficient input voltage of the generator will be indicated 
by a flashing LED "Start IN". The LED will turn off, as soon as the input voltage is sufficient or when the power requirement 
had dropped anyway due to a charged board battery. 
The charging converter simulates a larger consumer load at the generator/starter circuit to ensure an activation also with 
Euro 6 vehicles with intelligent generators, if required. 

 

 

Содержание VCC 1212-50

Страница 1: ...s excel by their compact design low weight high frequency switch mode technology and powerfully dimensioned power components for safe operation Significantly improved energy balance of the board batte...

Страница 2: ...ng and fuses of the customer which are already existing in the vehicle Only suitable for VCC 1212 50 page 4 Suitable for combination with electroblock EBL EVS with the existing cabling of the customer...

Страница 3: ...cross sections and lengths of the cables Never mix up the voltage sensor cables for start Vs and Vs and board Vb and Vb Insert fuses near the battery for protection of the cables Reverse battery 12 V...

Страница 4: ...12 50 The cabling and the fuses for the electroblock EBL provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually limit the maximum cur...

Страница 5: ...50 70 90 with full capacity The cabling and the fuses for the electroblock EBL provided by the customer are further used For this purpose insert a switching relay 12 V 60 A order No 2202 into the cabl...

Страница 6: ...y suitable for VCC 1212 50 The cabling with the fuses and the cutoff relay provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually lim...

Страница 7: ...to tables 1 The further cabling to the batteries including different cross sections is to be done directly at the relay The 12 V current requirement of the inverter might be higher than the output ca...

Страница 8: ...ntioned maximum values for Cable Length BOARD are only used to approx 2 3 VCC 1212 50 Cable Cross section Cable Length START In case of insulated body Cable Length Batt Fuse 2 Cable Protection Cable L...

Страница 9: ...ay in case of temporarily very high consumer current rates If not used leave the terminal blank The rating of the output is max 1 A and it is protected with a thermal fuse which resets itself after re...

Страница 10: ...age rates of 20 C 25 C being recommended by the battery manufacturers LiFePO4 Batteries Installation The thermal contact of sensor and inside temperature of the battery should be well Thus it should b...

Страница 11: ...temperature equalization for batteries in lead technology 1 Lead Acid Switch Position U1 14 40 V U2 13 50 V 2 6 h Universal charging program for acid lead acid batteries acc to DIN 57 510 VDE 0510 for...

Страница 12: ...emperature control adapted to lithium batteries Observe the instructions of the battery manufacturer An operation of the unit at a LiFePO4 battery without BMS Battery Management System and without equ...

Страница 13: ...U1 14 20 V U2 13 60 V 0 5 h Adapted to Victron LFP BMS 12 8 TransWatt TH 12 xxx of the indicated capacity rates Operation of the battery only with own BMS and prescribed safety circuit 7 LiFePO4 14 4...

Страница 14: ...ging port for the starter battery is existing in the system the function auxiliary charging of the charging converter is not required and should be switched off A Switch position to the left A Auxilia...

Страница 15: ...inuous signal at D without running engine might discharge the starter battery Increase of the charging capacity 12 50 V Reduction of the charging capacity 12 20 V Switching off threshold 12 00 V 30 se...

Страница 16: ...ellow If it is on Pilot lamp for the starter battery during operation If it is flashing The voltage of the starter battery is too low or too high only with D control Is flashing shortly every 2 sec Du...

Страница 17: ...uch as in EBL EVS bridges the charging converter Check connection plan Operation with EBL EVS etc m The charging converter changes permanently between active and quiescent condition D must arrive dire...

Страница 18: ...ion phase After that automatic switching to the following phase U1 4 During the phase U1 LED Main Charge is lighting the battery voltage will be kept constant on a high level The green LED Battery Ful...

Страница 19: ...ree from condensation water Never use the unit in locations where the risk of gas or dust explosion exists Open air operation of the unit is not allowed Lay the cables in a way that damage is avoided...

Страница 20: ...Ah 100 460 620 Ah 150 600 800 Ah LiFePO4 Charging Programs Stored in the Memory 4 4 4 Safety Charging Voltage at Battery Overtemperature 12 80 V 12 80 V 12 80 V Input T T for Battery Temperature Sens...

Отзывы: