5  "TR" Bypass Relay:

 Special case: In case of temporarily very high consumer current rates 

exceeding the maximum charger current of the charging converter, such as with operation of a 
body air-conditioner during driving with powerful inverter: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Instructions for faultless function of this option:

  Connect the charging converter VCC and the 

"TR" bypass relay with 2 x approx. 50 cm connection cables, cross-sections acc. to tables 1 (

**

). 

The further cabling to the batteries, including different cross-sections, is to be done directly at 

the relay! 

The 12 V current requirement of the inverter might be higher than the output capacity of the charging converter. Then, the 

charging converter activates automatically the high-performance relay, and the high consumer current can flow directly to 

the board battery, which will, however, not be charged, but must supply current instead. If the large consumer switches off, 

the charging converter separates that direct connection again automatically and resumes its (full) charging and control 
functions. 

Содержание VCC 1212-50

Страница 1: ...s excel by their compact design low weight high frequency switch mode technology and powerfully dimensioned power components for safe operation Significantly improved energy balance of the board batte...

Страница 2: ...ng and fuses of the customer which are already existing in the vehicle Only suitable for VCC 1212 50 page 4 Suitable for combination with electroblock EBL EVS with the existing cabling of the customer...

Страница 3: ...cross sections and lengths of the cables Never mix up the voltage sensor cables for start Vs and Vs and board Vb and Vb Insert fuses near the battery for protection of the cables Reverse battery 12 V...

Страница 4: ...12 50 The cabling and the fuses for the electroblock EBL provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually limit the maximum cur...

Страница 5: ...50 70 90 with full capacity The cabling and the fuses for the electroblock EBL provided by the customer are further used For this purpose insert a switching relay 12 V 60 A order No 2202 into the cabl...

Страница 6: ...y suitable for VCC 1212 50 The cabling with the fuses and the cutoff relay provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually lim...

Страница 7: ...to tables 1 The further cabling to the batteries including different cross sections is to be done directly at the relay The 12 V current requirement of the inverter might be higher than the output ca...

Страница 8: ...ntioned maximum values for Cable Length BOARD are only used to approx 2 3 VCC 1212 50 Cable Cross section Cable Length START In case of insulated body Cable Length Batt Fuse 2 Cable Protection Cable L...

Страница 9: ...ay in case of temporarily very high consumer current rates If not used leave the terminal blank The rating of the output is max 1 A and it is protected with a thermal fuse which resets itself after re...

Страница 10: ...age rates of 20 C 25 C being recommended by the battery manufacturers LiFePO4 Batteries Installation The thermal contact of sensor and inside temperature of the battery should be well Thus it should b...

Страница 11: ...temperature equalization for batteries in lead technology 1 Lead Acid Switch Position U1 14 40 V U2 13 50 V 2 6 h Universal charging program for acid lead acid batteries acc to DIN 57 510 VDE 0510 for...

Страница 12: ...emperature control adapted to lithium batteries Observe the instructions of the battery manufacturer An operation of the unit at a LiFePO4 battery without BMS Battery Management System and without equ...

Страница 13: ...U1 14 20 V U2 13 60 V 0 5 h Adapted to Victron LFP BMS 12 8 TransWatt TH 12 xxx of the indicated capacity rates Operation of the battery only with own BMS and prescribed safety circuit 7 LiFePO4 14 4...

Страница 14: ...ging port for the starter battery is existing in the system the function auxiliary charging of the charging converter is not required and should be switched off A Switch position to the left A Auxilia...

Страница 15: ...inuous signal at D without running engine might discharge the starter battery Increase of the charging capacity 12 50 V Reduction of the charging capacity 12 20 V Switching off threshold 12 00 V 30 se...

Страница 16: ...ellow If it is on Pilot lamp for the starter battery during operation If it is flashing The voltage of the starter battery is too low or too high only with D control Is flashing shortly every 2 sec Du...

Страница 17: ...uch as in EBL EVS bridges the charging converter Check connection plan Operation with EBL EVS etc m The charging converter changes permanently between active and quiescent condition D must arrive dire...

Страница 18: ...ion phase After that automatic switching to the following phase U1 4 During the phase U1 LED Main Charge is lighting the battery voltage will be kept constant on a high level The green LED Battery Ful...

Страница 19: ...ree from condensation water Never use the unit in locations where the risk of gas or dust explosion exists Open air operation of the unit is not allowed Lay the cables in a way that damage is avoided...

Страница 20: ...Ah 100 460 620 Ah 150 600 800 Ah LiFePO4 Charging Programs Stored in the Memory 4 4 4 Safety Charging Voltage at Battery Overtemperature 12 80 V 12 80 V 12 80 V Input T T for Battery Temperature Sens...

Отзывы: