How to set the

 

operating mode 

of the starter battery (IN, input side) 

The automatic control (activation) of the charging converter after the engine start can be executed in two different ways: 

 

In case of special applications, voltage-controlled by the increased voltage of the starter battery with running engine 
(not for EURO 6 vehicles!) 

 

Recommended with vehicle "D+" signal (generator active, recommended) or with ignition on (vehicle terminal 15). 

Table 4: 

Selector 

Switch 

 

IN Input Side

 of the Charging Converter: 

Set the operating range and the behaviour of the charging converter up to the starter 
circuit. Also refer to  
"Function of the Power Control at Starter Battery and Generator", page 17. 

 

1.

   Pure 

voltage control

 of the charging converter, leave terminal "D+" blank: 

Because of the high voltage thresholds, only to be used with "

Vs-

 and 

Vs+

" start sensor cables, 

sufficiently dimensioned cable cross-sections and powerful generator. 

 

The starter battery will not be discharged under any circumstances.

 

Increase of the charging capacity: 

> 13.50 V   

Reduction of the charging capacity: 

< 13.20 V   

Switching off threshold: 

< 13.00 V   30 sec. 

 

2.

   Pure 

voltage control

 of the charging converter, leave terminal "D+" blank: 

Like 

1.

  However, lower switching thresholds, negligible load of the starter battery. 

Increase of the charging capacity: 

> 13.30 V   

Reduction of the charging capacity:  

< 13.00 V   

Switching off threshold: 

< 12.80 V   30 sec.

 

 

3.

   Activation of the Charging Converter by 

Control Signal

 "D+" or ignition "Kl.15". 

Because of the average-high voltage thresholds, only to be used with "

Vs-

 and 

Vs+

" starter sensor 

cables, sufficiently dimensioned cable cross-sections and powerful generator. 

Note: A continuous signal at "D+" without running engine might discharge the starter battery! 

Increase of the charging capacity: 

> 12.50 V   

Reduction of the charging capacity:   

< 12.20 V   

Switching off threshold: 

< 12.00 V   30 sec. 

  

4.

   

Activation of the Charging Converter by 

Control Signal "D+"

 or ignition "Kl.15".

 

This operating mode is particularly provided for 

EURO standard 6, 6+ vehicles

 with intelligent 

generators, energy management, start/stop automatics, strongly varying voltage of 
generator/starter battery during energy recovery etc. 
Generally recommended for operation with electroblock 

EBL

, EVS. 

The start sensor cables "

Vs-

 and 

Vs+

" are not required, if the values in the 

tables 1

 for "

Cable 

Length "+ START"

 are only used to approx. 3/4. 

If the cables are long (losses), these cables are, however, advantageous for full charging capacity. 

Control the control input "D+" either with KL.15 (ignition ON) or 

more safely

 connect it to 

D+

 of 

the vehicle (generator "active"), since in case of a continuous signal (ignition ON) without running 
engine the starter battery can be 

strongly

 discharged! 

Increase of the charging capacity: 

11.70 V

   

Reduction of the charging capacity:  

11.40 V

   

Switching off threshold: 

11.20 V

   30 sec.

 

 

Option:

  

Parallel Connection of Two Charging Converters: 

An increase of the charging capacity for large battery systems or high loads (such as operation of an air-conditioning system 
with low capacity units) can be realized by parallel connection of two identical units. Couple the connections and set 

both 

units

 to switch position 

"4"

 according to table 4. 

The separately laid "

Vs-

 and 

Vs+

" start sensor cables are to be distributed to the inputs of both units, also the 

"D+" control signal. 
Due to the occurring high current rates, the required 

cable cross-sections

 of the power supply connections 

must be multiplied by two, or they must be 

observed (tables 1)

 absolutely in case of separate laying.

 

 

 

Содержание VCC 1212-50

Страница 1: ...s excel by their compact design low weight high frequency switch mode technology and powerfully dimensioned power components for safe operation Significantly improved energy balance of the board batte...

Страница 2: ...ng and fuses of the customer which are already existing in the vehicle Only suitable for VCC 1212 50 page 4 Suitable for combination with electroblock EBL EVS with the existing cabling of the customer...

Страница 3: ...cross sections and lengths of the cables Never mix up the voltage sensor cables for start Vs and Vs and board Vb and Vb Insert fuses near the battery for protection of the cables Reverse battery 12 V...

Страница 4: ...12 50 The cabling and the fuses for the electroblock EBL provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually limit the maximum cur...

Страница 5: ...50 70 90 with full capacity The cabling and the fuses for the electroblock EBL provided by the customer are further used For this purpose insert a switching relay 12 V 60 A order No 2202 into the cabl...

Страница 6: ...y suitable for VCC 1212 50 The cabling with the fuses and the cutoff relay provided by the customer are further used VCC 1212 50 The switches IN Limit see table 3 page 14 can be used to eventually lim...

Страница 7: ...to tables 1 The further cabling to the batteries including different cross sections is to be done directly at the relay The 12 V current requirement of the inverter might be higher than the output ca...

Страница 8: ...ntioned maximum values for Cable Length BOARD are only used to approx 2 3 VCC 1212 50 Cable Cross section Cable Length START In case of insulated body Cable Length Batt Fuse 2 Cable Protection Cable L...

Страница 9: ...ay in case of temporarily very high consumer current rates If not used leave the terminal blank The rating of the output is max 1 A and it is protected with a thermal fuse which resets itself after re...

Страница 10: ...age rates of 20 C 25 C being recommended by the battery manufacturers LiFePO4 Batteries Installation The thermal contact of sensor and inside temperature of the battery should be well Thus it should b...

Страница 11: ...temperature equalization for batteries in lead technology 1 Lead Acid Switch Position U1 14 40 V U2 13 50 V 2 6 h Universal charging program for acid lead acid batteries acc to DIN 57 510 VDE 0510 for...

Страница 12: ...emperature control adapted to lithium batteries Observe the instructions of the battery manufacturer An operation of the unit at a LiFePO4 battery without BMS Battery Management System and without equ...

Страница 13: ...U1 14 20 V U2 13 60 V 0 5 h Adapted to Victron LFP BMS 12 8 TransWatt TH 12 xxx of the indicated capacity rates Operation of the battery only with own BMS and prescribed safety circuit 7 LiFePO4 14 4...

Страница 14: ...ging port for the starter battery is existing in the system the function auxiliary charging of the charging converter is not required and should be switched off A Switch position to the left A Auxilia...

Страница 15: ...inuous signal at D without running engine might discharge the starter battery Increase of the charging capacity 12 50 V Reduction of the charging capacity 12 20 V Switching off threshold 12 00 V 30 se...

Страница 16: ...ellow If it is on Pilot lamp for the starter battery during operation If it is flashing The voltage of the starter battery is too low or too high only with D control Is flashing shortly every 2 sec Du...

Страница 17: ...uch as in EBL EVS bridges the charging converter Check connection plan Operation with EBL EVS etc m The charging converter changes permanently between active and quiescent condition D must arrive dire...

Страница 18: ...ion phase After that automatic switching to the following phase U1 4 During the phase U1 LED Main Charge is lighting the battery voltage will be kept constant on a high level The green LED Battery Ful...

Страница 19: ...ree from condensation water Never use the unit in locations where the risk of gas or dust explosion exists Open air operation of the unit is not allowed Lay the cables in a way that damage is avoided...

Страница 20: ...Ah 100 460 620 Ah 150 600 800 Ah LiFePO4 Charging Programs Stored in the Memory 4 4 4 Safety Charging Voltage at Battery Overtemperature 12 80 V 12 80 V 12 80 V Input T T for Battery Temperature Sens...

Отзывы: