10
TROUBLESHOOTING
If latches do not retract when pushpad is depressed:
Remove cover plate from edge of door
Pull down on
top spool screw
. If the top latch fails to actuate, readjust top spool (Steps 4d-1 thru 4d-4).
Pull up on
bottom spool screw
. If the bottom latch fails to actuate, readjust bottom latch clearance (Steps 8b-1 thru 8b-4).
If both actuate and the door is not functioning, proceed to next check.
Remove center case cover
Check
lift finger screws
to ensure they are still fully seated. If unseated, loosen
locking
screw
, and while applying pressure to the head of the
lift finger screw
to
seat it, tighten locking screw. If door is not functioning, proceed to next step.
With
both
lift finger screws
fully seated, loosen
top and bottom locking
screws
, turn
lift finger screws
clockwise to end of travel, and repeat
device adjustment, Step 6.
If bottom latch pin does not move during Step 6b-2:
Loosen
bottom spool screw
10 turns.
Seated
Unseated