Text block:
The text block is used to read or write texts via the data block.
7.4.7 The PKE Field
The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU:
Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Parameter commands master
⇒
slave
Bit no.
Parameter command
15
14
13
12
0
0
0
0
No command
0
0
0
1
Read parameter value
0
0
1
0
Write parameter value in RAM (word)
0
0
1
1
Write parameter value in RAM (double word)
1
1
0
1
Write parameter value in RAM and EEprom (double word)
1
1
1
0
Write parameter value in RAM and EEprom (word)
1
1
1
1
Read/write text
7 RS-485 Installation and Set-up
Automation VT Drive FC322 Design Guide
204