Troubleshooting 

 
Most error messages can be viewed in the history log of Mach4 and can indicate problems with the configuration 
or the runtime operation. 
 

 

 

 

 

The system disarms when calling the M3 command 

 

Cause 

Solution 

One of the THC settings may be bad. 

Review the THC settings on the ArcPro screen and make 
sure that the 

[THC On]

 is enabled and mapped to a 

digital input on the motion controller.  

The 

[ArcOK]

 or 

[DIGITIZE]

 signal is 

currently active. 
 

Check the Mach4 Input signal mapping, and make sure 
that the polarities (Active Low/High), are set to the 
correct values. Inspect the wiring and make sure that 
the LEDs on the Arc Pro screen toggle properly. 

The controller was busy executing another 
motion sequence. 
 

In most scenarios, this error shouldn’t occur. Check the 
GCode File or MDI command being executed before the 
M3 command. 

The probe move reached the indicated 
limit without detecting the digitize signal. 

Check that the 

[Digitize]

 signal in Mach4 is mapped to 

the correct digital input, and that the 

[Digitize]

 signal 

toggles correctly by checking the signal state in the 
diagnostic tab on the Mach4 screen. 

 

The THC feature is currently not activated 
on the unit. 

Please contact the vendor of your unit, or Vital System 
Inc. 

 

NOTE: It is also recommended to go 
through th

wiring diagram

 for safely 

connecting the digitize sensor to the 

motion controller. 

NOTE: Please follow the proper setup instructions for wiring, Mach4 

configuration, and the setting the on-screen THC parameters before attempting 

any tests. 

Содержание ArcPro Plasma

Страница 1: ...ystems Inc 1 www vitalsystem com ArcPro Plasma User Guide Document Revision 3 0 Updated July 23 2020 2020 Vital Systems Inc Atlanta GA USA For more information please visit the product web page www vi...

Страница 2: ...12 MACH4 Plasma Screen Setup 13 1 USEANALOGVOLTAGEFORARCOK 13 USE EXTERNAL ARC OK 14 Screen Settings 15 Characteristics 16 Screen Definitions 17 THC TAB 17 THC CUT START SETTINGS 18 Troubleshooting 2...

Страница 3: ...will hold no one other than myself responsible for mistakes errors material loss personal damages secondary damages faults or errors of any kind caused by any circumstance any bugs or any undesired re...

Страница 4: ...Mach4 CNC Software This document DOES NOT serve as a primer or tutorial for the use of Mach4 As such readers without basic understanding of Mach4 and other software components not associated with Vita...

Страница 5: ...Digitize Sensor Ohmic Probe NOTE It is highly recommended to follow the circuit diagram below when using a Digitize sensor on the torch head Because a Plasma Torch uses high voltage for cutting volta...

Страница 6: ...2020 Vital Systems Inc 6 www vitalsystem com Connecting NPN Digitize Sensor Ohmic Probe Integra 7866 3 9K 1W GND Earth GND Integra Input 3 Digitize 0 47uF 1kV HiCON Integra Earth...

Страница 7: ...ma profile available on the sidebar from the product website http www vitalsystem com arcpro Open Mach4 loader and click on Import Profile Browse for the downloaded profile m4prof file and click Open...

Страница 8: ...2020 Vital Systems Inc 8 www vitalsystem com Mach4 I O Configuration...

Страница 9: ...elay starts Immediately following the pierce delay the XY motion starts and the torch height control begins once the THC delay expires All these steps are done by the M3 Macro script provided in the M...

Страница 10: ...ntact the material to determine the material height probe Step 3 The torch head lifts to ignition height and turns on Step 4 The Arc Ok signal is detected and the torch moves to pierce height Step 5 T...

Страница 11: ...ead the plasma tip voltage This adapter accepts 0 to 10volts from the Plasma unit You must select the proper divider to reduce the tip voltage which are usually in the 300 volts range down to 0 10 vol...

Страница 12: ...nect the 7866 to the network and launch the VSI Device Manager Select the controller and go to the HiCON tab Make sure to uncheck J7 J8 for switching to Step Dir channel and justselect the Enable J7 T...

Страница 13: ...ArcOK by using Analog Voltage or an external ArcOK signal can be used as an input to the HiCON 7866 Motion Controller Both the cases are described as follows 1 USEANALOGVOLTAGE FORARCOK Use Mach4 to l...

Страница 14: ...THC sequence will only continue if it sees the Tip Voltage value is within this range and the THC On led is lit USE EXTERNAL ARC OK All the settings remain same as above except for the Use Analog volt...

Страница 15: ...screen has Tip Voltage Reading and AnalogVoltage Multiplier The Tip Voltage displays the value of the analog reading multiplied by the value given in the Analog voltage multiplier The value of the Ana...

Страница 16: ...system com Characteristics The Response delay of the 77ISO board is hardly noticeable due toits fast response time as short as 6Ms This ensures that the THC operation takes place with fast Tipvoltage...

Страница 17: ...y and cutting manually Under normal conditions THC is enabled when the torch is on and it is turned off when the torch is off THC On Arc OK and is associated with an LED Up Down buttons that control T...

Страница 18: ...not have a probe input there is a button on the THC Cut Start to omit the material touch off as part of the M3 sequence Special attention must be taken when the touch off has been omitted The top of...

Страница 19: ...in milliseconds allowed to complete piercing material used in M3 This value can be found in user manuals for Plasma units Max Maximum height THC will move the torch up to while trying to get to the ta...

Страница 20: ...een toggle properly The controller was busy executing another motion sequence In most scenarios this error shouldn t occur Check the GCode File or MDI command being executed before the M3 command The...

Страница 21: ...he displayed coordinates have a Work Offset applied Refrain from using the Zero X Y or Z buttons and instead use the appropriate homing routine to go back to machine zero or manually jog or issue a GC...

Страница 22: ...ight that the torch will be allowed to move while cutting Set these two parameters to larger values to allow a greater window for height correction The THC Speed is set to a very small value This para...

Отзывы: