PREMIUM DSP 40-80 KVA PF0.9 3/3 - UPS www.visionups.com
25
3.2.5 COMMAND MENU
This menu contains UPS commands be carefull while using commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
<ENTER> button applies the related command.
COMMAND MENU
Page 1 (Level 1)
ENTER <BYPASS>
ENTER transfer the load to bypass
ENTER <BOOST>
ENTER start boost charge mode
ENTER B.TEST > 405
ENTER start short battery test
RELAY TEST:OFF
Left and right test dry contact relays
ENTER : MODEM INIT
ENTER initialize dialup modem
ALARM SOUND: ON/OFF
Press enter to select
disable alarm buzzer
3.2.6 TIME MENU
You can see Time and date information of the RTC in the UPS ,also you can set date and time from
this menu.
Follow the arrows to set date and time
3.2.7 SERVICE MENU
This menu contains some helpfull service information and some commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
SERVİCE MENU
Page 1 (Level 1)
HOURMETER:00075
Total operating hour of the UPS
MAXLOAD:015 020 025 %
From power on recorded maximum power
ENTER<FAULT RESET>
ENTER fault reset
FAN MAINT: 01000
Remaining hours to FAN maintenance
BAT MAINT :01200
Remaining hours to battery maintenance
GEN.MAINT: 00500
Remaining hours to general maintenance
LOGOUT: --
ENTER Exit from service login status
If maintenance counters are disabled CANCEL word is shown.