PREMIUM DSP 40-80 KVA PF0.9 3/3 - UPS www.visionups.com
28
A08 ON MAINTENANCE
Alarm
Maintenance by-pass switch on
A09 MANUAL BYPASS
Alarm
Load is transferred to by-pass from front panel
A10 BATTERY LOW SHUT
Alarm
Inverter measured battery voltage is low (shutdown level)
A11 REPO STOP
Alarm
External REPO input signal sensed
A12 DC BALANCE BAD
Alarm
Before inverter start fitler capacitors dont discharged
A13 PEAK CURRENT
Alarm
Very high current at the UPS output
A14 INV NOT START
Alarm
Inverter module start failed
A17 BYPASS FAILURE
Warning By-pass input voltage failure
A18 BYPASS VOLT
Warning By-pass input voltage out of tolerance
A19 BYP FREQ.TOLER
Warning By-pass input frequency out og tolerance
A20 OVERLOAD
Warning Currently the load exceeded 100% capacity
A21 OVERTEMP
Warning Currently inverter power modul heatsink temperature is high
A22 OUTPUT OFF
Warning There is no UPS output voltage
A23 ON BYPASS
Warning Load is on bypass
A24 REVERSE CURRENT
Warning Regenerative backfeed to UPS output
A25 INV RESET
Warning Inverter module power on
A26 BATTERY LOW
Warning Batteries are going to full discharge
A27 GENERATOR MODE
Warning Generator set is running
A28 O/P PHASE LOSS
Warning Anyone of the UPS output phases there is no voltage
A29 SYNCHRON BAD
Warning Inverter is not synchron to by-pass input
A30 SHORT CIRCUIT
Warning Short circuit occured at the UPS output currenty normal
A31 OUTPUT SWITCH
Warning Output switch of the UPS is off
A32 SERVICE LOGIN
Warning Service login active
A34 BYP ROTATE PHASE
Warning By-pass phase sequency incorrect
A35 INV STOP
Warning Inverter module interrupted
A36 INV DC DOWN
Warning DC BUS voltage is less then 120 volts DC
A37 AC CURR LIMIT
Warning Inverter output current limited
A38 FUSE FAILURE
Warning Any fuse in UPS is blowned
A39 PSP FAILURE
Alarm
Inverter control board power supply out of tolerant
A40 INVERTER START
Warning Inverter is in soft start stage wait for finish
A43 USER LOGIN
Warning User logged in to UPS
A45 SERV.PASSWORD
Fault
For UPS startup service password required
If any alarm shown on the LCD panel without A00 and R00 message UPS will start automatically if the
conditions are normal. But if you see A00 or R00 code with any alarm together you must CALL
SERVICE !
If the message is warning UPS continues to run there is no problem.
To support technical service status cods are used, each status code tells different event to us.