PREMIUM DSP 40-80 KVA PF0.9 3/3 - UPS www.visionups.com
10
1.4 Technical Specifications
MODEL
DSP340
DSP360
DSP380
Output (KVA)
40 kVA
60 kVA
80 kVA
Output (KW)
36 kW
54 kW
72 kW
Output Power Factor
0,9
INPUT
Number of Phases
3 Phase + Neutral
Input Voltage
220/380, 230/400 or 240/415 Vac
Input Voltage Tolerance
+20% , -25% (+15% at 240/415Vac)
Input Power Factor (PF)
0,98 - 0,99 (at full load)
Input THDI
<= 5% (at full load)
Input Frequency
50 Hz.
5%
By-pass Voltage
220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
By-pass Frequency
50 Hz.
2%
RFI Level
EN62040-2
OUTPUT
Number of Phases
3 Phase + Neutral
Output Voltage
220/380, 230/400 or 240/415 Vac
Output Voltage Tolerance
1%
Output Frequency
50 Hz.
Output Frequency Tolerance (Synchronous)
2%
Output Frequency Tolerance (Battery)
0,2%
Efficiency (100% Load)
up to 94%
Load Crest Factor
3:1
Output Voltage THD (linear load)
<3%
Overload
125% Load 10min. , 150% Load 1min.
BATTERY
Total Number
60 blocks 12V (2x30 serial 60 batteries)
Float Charge Voltage (25
0
C)
405V DC
End of Discharge Voltage
300V DC
Battery Test
Automatic and Manual
Boost Charge
Available
COMMUNICATION INTERFACES
RS232 Com Port
2 each standard (COM1 and COM2)
External Temperature Measurement Input
Available (standard)
RS485 Comm. Port
Optional
Remote Monitoring Panel
Optional
SNMP Adapter
Optional
Modbus Adapter
Optional
Alarm Relay Contacts
4 each dry contacts (function programmable) 8 optional
Digital Inputs
2 each optional
Emergency Power-Off Input
Available (standard)
ENVIRONMENT
Operating Temperature
0
– 40
0
C
Operating Humidity
<= %90 (non-condensing)
Acoustic Noise
<62dB
Dimensions (WxDxH) (mm)
515 x 855 x 1450
Device Type and Protection Class
Class 1
– IP20
Weight (Without Batteries) (app. kgs)
175
180
194