PREMIUM DSP 40-80 KVA PF0.9 3/3 - UPS www.visionups.com
27
Rectifier module alarm codes
REC CODE = XXXX
XXXX SYSTEM fault occured at the rectifer module
R00 REC FAULT = XXXX
Fault
Rectifier AC input voltage is high
CALL SERVICE !
R01 AC INPUT HIGH
Alarm
Rectifier AC input voltage is low
R02 LINE FAILURE
Alarm
Rectifier DC output voltage is high
R03 DC BUS HIGH
Alarm
The rectifier DC output voltage is high, rectifier stop
R05 FREQ TOLER
Alarm
Rectifier input frequcny out of tolerant
R06 OVERTEMPERATURE
Alarm
Rectifier heatsink temperature high
R07 BLACKOUT
Alarm
Short voltage blackout at rectifier AC input
R08 I/P OVERCURRENT
Alarm
Rectifier IGBT saturation alarm
R09 ROTATE PHASE
Alarm
Rectifier input phase sequency incorrect
R14 PFC MANUAL STOP
Alarm
Inverter module stopped rectifier
R15 DC LOW
Alarm
DC BUS voltage is lower then DC rectifier start voltage
R17 BATTERY TEST
Warning Currently battery test is performing
R18 BOOST CHARGE
Warning Currently rectifier is in boost charge mode
R19 AC HIGH
Alarm
AC Peak voltage is bigger then 20% of nominal range
R20 INPUT CB OPEN
Warning Input CB is off
R21 PFC STOP
Warning Currently Rectifier module stop
R22 POS CHG LIMIT
Warning (+)Battery charge current limited
R23 NEG CHG LIMIT
Warning (-)Battery charge current limited
R24 WAITING DC BUS
Warning Rectifier is waiting DC BUS to raise for startup
R25 BATTERY FAILURE
Warning Battery test failed
R26 BATT TEMP SENSOR
Warning Battery temperature sensor is defected or not connected
R27 BATT TEMP HIGH
Warning Battery ambient temperature is high
R29 PFC RESET
Warning Rectifier module power on
R30 PLEASE WAIT
Warning Rectifier waits as adjusted startup delay
R31 RECTIFIER START
Warning Rectifier is in soft start stage
Panel module alarm codes
L01 TH1 TEMP HIGH
Warning TH1 temperature is high
L02 TH2 TEMP HIGH
Warning TH2 temperature is high
L03 TH1 TEMP LOW
Warning TH1 temperature is low
L04 TH2 TEMP LOW
Warning TH2 temperature is low
L05 FAN MAINT
Warning FAN maintenance time
L06 BATTERY MAINT
Warning Battery maintenance time
L07 OPT MAINTENANCE
Warning Optional maintenance time
L08 TH1 SENSOR FAIL
Warning TH1 temperature sensor failure
L09 TH2 SENSOR FAIL
Warning TH2 temperature sensor failure
L10 ENTER FAULT RESET Warning UPS is waiting fault reset for startup
L11 BATT CB OPEN
Warning External interactive battery switch is off
L12 GENERAL MAINT
Warning General maintenance time
L13 PFC CAN COMM ERR
Warning PFC module CAN communication timeout
L14 INV CAN COMM ERR
Warning INV module CAN communication timeout
Inverter module alarm codes
INV CODE = 0XXX
Current inverter modüle status code
A00 INV FAULT = XXXX
Hata
XXXX fault occured at the inverter module
CALL SERVICE !
A01 O/P OVERCURRENT
Alarm
IGBT saturation alarm on inverter module
A02 OVERTEMP SHUT
Alarm
Overtemperature at inverter power module
A03 BATT HIGH
Alarm
Inverter module measured battery voltage high
A04 OUTPUT V.LOW
Alarm
Inverter output voltage is low
A05 OUTPUT V.HIGH
Alarm
Inverter output voltage is high
A06 OVERLOAD SHUT
Alarm
Overload at UPS output
A07 SHORT CIRCUIT
Alarm
Short circuit at UPS output