Chapter 2 Decentral block periphery CAN-Bus CANopen
Manual VIPA System 100V
2-34
HB100E - SM-CAN - Rev. 15/02
Index
Sub-
index
Name
Type
Attr. Map.
Default value Meaning
0x1017
0 Producer
heartbeat time
Unsigned16 rw
N
0x0000
Defines the cycle time of
heartbeat in ms
Index
Sub-
index
Name
Type
Attr. Map.
Default value
Meaning
0x1018
0
Identity Object
Unsigned8
ro
N
0x04
Contains general
Information about the
device (number of
entries)
1
Vendor ID
Unsigned32 ro
N
0xAFFEAFFE
Vendor ID
2
Product Code
Unsigned32 ro
N
VIPA 153-4CF00 =
0x1534CF00
VIPA 153-4CH00
=
0x1534CA00
VIPA 153-6CL10 =
0x1536CB10
VIPA 153-6CH00
=
0x1536CA00
Product Code
3
Revision Number Unsigned32
ro
N
Revision Number
4
Serial Number
Unsigned32
ro
N
Serial Number
Index
Sub-
index
Name
Type
Attr. Map.
Default value Meaning
0x1029
0
Error behavior
Unsigned8
ro
N
0x02
Number of error classes
1 Communication
Error
Unsigned8 ro N
0x00
Communication
error
2 Manufacturer
specific error
Unsigned8
ro
N
0x00
Manufacturer specific error
As soon as a device error is detected in the "operational" state, the module
should change automatically to "pre-operational" state.
Otherwise, if you for e.g. implemented Error behavior, the module may be
configured to switch to "stopped" state at an error event.
The following error classes may be shown:
0 = pre-operational
1 = no state change
2 = stopped
Producer
Heartbeat Time
Identity Object
Error Behavior