Manual VIPA System 100V
Chapter 2 Decentral block periphery CAN-Bus CANopen
HB100E - SM-CAN - Rev. 15/02
2-25
0x05030000
Toggle bit not alternated
0x05040000
SDO protocol timed out
0x05040001
Client/server command specifier not valid or unknown
0x05040002
Invalid block size (block mode only)
0x05040003
Invalid sequence number (block mode only)
0x05040004
CRC error (block mode only)
0x05040005
Out of memory
0x06010000
Unsupported access to an object
0x06010001
Attempt to read a write only object
0x06010002
Attempt to write a read only object
0x06020000
Object does not exist in the object dictionary
0x06040041
Object cannot be mapped to the PDO
0x06040042
The number and length of the objects to be mapped would
exceed PDO length
0x06040043
General parameter incompatibility reason
0x06040047
General internal incompatibility in the device
0x06060000
Access failed due to a hardware error
0x06070010
Data type does not match, length of service parameter
does not match
0x06070012
Data type does not match, length of service parameter too
high
0x06070013
Data type does not match, length of service parameter too
low
0x06090011
Sub-index does not exist
0x06090030
Value range of parameter exceeded (only for write access)
0x06090031
Value of parameter written too high
0x06090032
Value of parameter written too low
0x06090036
Maximum value is less than minimum value
0x08000000 general
error
0x08000020
Data cannot be transferred or stored to the application
0x08000021
Data cannot be transferred or stored to the application
because of local control
0x08000022
Data cannot be transferred or stored to the application
because of the present device state
0x08000023
Object dictionary dynamic generation fails or no object
dictionary is present (e.g. object dictionary is generated
from file and generation fails because of an file error)
SDO Error-Codes