Manual VIPA System 100V
Chapter 2 Decentral block periphery CAN-Bus CANopen
HB100E - SM-CAN - Rev. 15/02
2-9
The digital input section a System 100V module collects the binary control
signals of the process level and transmits them to the leading CANopen
slave.
Every input channel shows its status via a green LED with a time delay of
max. 3ms. The nominal input voltage is DC 24V. Hereby 0...5V are
recognized as signal state "0" and 15...28.8V as signal state "1". More
information about the installation of the input section is to find under "Circuit
diagrams".
LED
.0... .7
Description
LEDs (green)
I+0.0 to I+0.7
starting with ca. 15V the
signal "1" is recognized
and the according LED is
addressed
DI 8xDC24V
.0
.1
.2
.3
.4
.5
.6
.7
1
2
3
4
5
6
7
8
9
I0
Pin
1
2
3
4
5
6
7
8
9
10
Assignment
not used
Input I+0.0
Input I+0.1
Input I+0.2
Input I+0.3
Input I+0.4
Input I+0.5
Input I+0.6
Input I+0.7
Ground
DC 24V
M
internal
V-Bus
Opto coupler
LED
Input
Input section
Status monitor
pin assignment
Schematic
diagram
input section