Manual VIPA System 200V
Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44
3-19
V-bus delayed acknowledgment
Length: 2
Reading or writing from/to digital modules failed
Byte
Bit 7 ... Bit 0
0
2Bh: V-bus delayed acknowledgment
System 200V diagnostic alarm
Length:
16
Byte
Bit 7 ... Bit 0
0
32h: System 200V diagnostic alarm
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2 ... 14 Data diagnostic alarm
System 200V process alarm
Length:
16
Byte
Bit 7 ... Bit 0
0
33h: System 200V process alarm
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2 ... 14 Process alarm data
New DP address assigned
Length:
2
When the slave has received the service with "Set Slave Address" it sends
the respective diagnostic message and re-boots. The slave will then
become available on the bus under the new address.
Byte
Bit 7 ... Bit 0
0
3Ch: new DP address has been assigned
Slave status is READY
Length: none (internal only)
The READY status of the slave is only used internally and is not transmitted
via the PROFIBUS.
Byte
Bit 7 ... Bit 0
0
3Dh: slave status is READY
Slave status is DataExchange
Length: none (only internal)
The DataExchange status of the slave is only used internally and is not
transmitted via the PROFIBUS.
Byte
Bit 7 ... Bit 0
0
3Eh: slave status is DataExchange
2Bh
32h
33h
3Ch
3Dh
3Eh
Содержание IM 253 DP Series
Страница 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Страница 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...