Measuring type Thermocouple
:
compensation external, linear (
Measuring type coding: 1110b
)
compensation internal, linear (
Measuring type coding: 1110b
)
Measuring range Range / Representation in °C (0.1°C/digit)
Range
coding
Type J
[
Fe-Cu-Ni IEC
]
1450°C
= End Overdrive region
(14500)
-210...1200°C = Nominal range
(-2100... 12000)
-210°C
= End Underdrive region
(-2100)
0101b
Type K
[
Ni-Cr-Ni
]
1622°C
= End Overdrive region
(16220)
-270... 1372°C = Nominal range
(-2700... 13720)
-270°C
= End Underdrive region
(-2700)
1000b
Type N
[
Ni-Cr-Si
]
1550°C
= End Overdrive region
(15500)
-270...1300°C = Nominal range
(-2700...13000)
-270°C
= End Underdrive region
(-2700)
0001b
Type E
[
Ni-Cr - Cu-Ni
]
1200°C
= End Overdrive region
(12000)
-270...1000°C = Nominal range
(-2700...10000)
-270°C
= End Underdrive region
(-2700)
0010b
Type L
[
Fe-Cu-Ni
]
1150°C
= End Overdrive region
(11500)
-200...900°C = Nominal range
(-2000...9000)
-200°C
= End Underdrive region
(-2000)
0110b
Type T
[
Cu-Cu-Ni
]
540
= End Overdrive region
(5400)
-270...400
= Nominal range (-2700...4000)
-270
= End Underdrive region
(-2700)
0111b
1)
Type R
[
PtRh-Pt
]
2019
= End Overdrive region
(20190)
-50...1769
= Nominal range (-500...17690)
-170
= End Underdrive region
(-1700)
0011b
1)
Type S
[
PtRh-Pt
]
2019
= End Overdrive region
(20190)
-50...1769 =
Nominal
range (-500...17690)
-170
= End Underdrive region
(-1700)
0100b
1)
Type B
[
PtRh-PtRh
]
2070
= End Overdrive region
(20700)
0...1820
= Nominal range (0...18200)
-120
= End Underdrive region
(-1200)
0000b
1)
Type C
[
PtRh-Pt
]
2500
= End Overdrive region
(25000)
0...2315
= Nominal range (0...23150)
-120
= End Underdrive region
(-1200)
1010b
1)
Measuring type Thermocouple:
compensation external (
Measuring type coding: 1011b
)
compensation internal (
Measuring type coding: 1010b
)
The evaluated thermo electromotive force is added to the force of the internal or external
reference junction and is mapped to the 80mV measuring range.
Measuring range
Range / Representation
Range
coding
Type J
[
Fe-Cu-Ni IEC
]
0101b
Type K
[
Ni-Cr-Ni
]
1000b
...
and so on
(see above)
94.071mV
= End Overdrive region
(32511)
- 80...80mV
= Nominal range
(-27648...27648)
- 94.074mV
= End Underdrive region
(-32512)
.
.
.
Type C
[
PtRh-Pt
]
1010b
1)
1)
The measuring range is available starting with firmware version V. 1.3.8. Since this measuring range is
not supported by the Siemens SIMATIC manager, the parameterization only takes place exclusively at run
time.
Содержание HB130E SM
Страница 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Страница 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Страница 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Страница 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...