Chapter 3   Digital Input Modules

 

Manual VIPA System 300V 

3-4 

 

HB130E - SM - Rev. 07/44 

DC 24V

M

intern

Bus

Optocoupler

LED

Input module

 

 

 
 

Module name 

VIPA 321-1BH01 

Dimensions and weight 

 

Dimensions WxHxD 

40x125x120mm 

Weight 200g 
Data for specific module 

 

Number of inputs 

16 

Programming specifications 

 

Input data 

2Byte 

Voltages, Currents, Potentials 

 

Isolation  
    - between channels and backplane bus 

yes 

Isolation tested with 

DC 500V 

Current consumption 

 

    - from the backplane bus 

25mA 

Power dissipation of the module 

3.5W 

Status, Interrupts, Diagnostics 

 

Status display 

green LED per channel 

Data for selecting a sensor 

 

Input voltage 

 

    - Rated value 

DC 24V 

    - for Signal "1" 

15 ... 28.8V 

    - for Signal "0" 

0 ... 5V 

Input current 

 

  - for Signal "1" 

7mA 

Input delay 

 

    - from "0" to "1" 

3ms 

    - from "1" to "0" 

3ms 

Connection of 2-wire-BEROs 

possible 

    - Permitted bias current 

1.5mA 

Schematic 
diagram 

Technical Data 

Содержание HB130E SM

Страница 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...

Страница 2: ...Lerrzeichen...

Страница 3: ...examined to ensure that it conforms with the described hardware and software However discrepancies can not be avoided The specifications in this manual are examined regularly and corrections will be i...

Страница 4: ...ation and assembly guide lines All information that you need for installation and cabling of a PLC with components of the System 300V may be found in this chapter Chapter 3 5 Digital in output modules...

Страница 5: ...2xDC 24V 1A 4 13 322 5FF00 DO 8xAC 120 230V 2A 4 16 322 1HH00 DO 16xRelay 4 21 Chapter 5 Digital Input Output Modules 5 1 System overview 5 2 Security hints for DIO modules 5 2 323 1BH00 DIO 16xDC 24V...

Страница 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...

Страница 7: ...e specific topic This manual provides the following guides An overall table of contents at the beginning of the manual An overview of the topics for every chapter An index at the end of the manual The...

Страница 8: ...ve environments EX zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using...

Страница 9: ...er also contains general information about the System 300V like measurements hints for installation and the environmental conditions Below follows a description of Safety information for the User Comp...

Страница 10: ...maged in this way are normally not immediately recognized The according error may occur only after a while of operation Modules that have been damaged by electrostatic discharges can fail after a temp...

Страница 11: ...dules of the VIPA System 300V are design compatible to Siemens Due to the compatible backplane bus it is no problem to mix the modules from VIPA and Siemens The CPUs of the System 300V are instruction...

Страница 12: ...are configuration you transfer your project into the CPU via MPI Another component of the decentral system is the CAN Slave It allows the link up to the fieldbus system CANopen A large number of perip...

Страница 13: ...power supply This power supply requires DC 24V In addition to the electronics on the bus coupler the supply voltage is also used to power any modules connected to the backplane bus Please note that t...

Страница 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...

Страница 15: ...stallation and the cabling of a process control with the components of the System 300V The following text describes General overview Steps of installation and cabling EMC guidelines for installing a S...

Страница 16: ...included in the delivery of the peripheral modules G 122 Order number A B C VIPA 390 1AB60 160mm 140mm 10mm VIPA 390 1AE80 482mm 466mm 8 3mm VIPA 390 1AF30 530mm 500mm 15mm VIPA 390 1AJ30 830mm 800mm...

Страница 17: ...07 44 2 3 Installation dimensions Here follows all the important dimensions of the System 300V 1tier width WxHxD in mm 40 x 125 x 120 2tier width WxHxD in mm 80 x 125 x 120 65mm 40mm 122 mm 125 mm 125...

Страница 18: ...MRES PLC X1 VIPA Muster PB M X5 X2 X3 PS DVI CF MPI PB DP CPU 317 BM X 2 3 4 DC 24V VIPA 321 1BH00 DI 16xDC24V X 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 SM321 VIPA 307 2EA00 PS 307 6 X 2 3 4 IN AC 100 2...

Страница 19: ...file rail and pull it to the left side to the grounding bolt of the profile rail Fix the power supply by screwing Take a bus coupler and click it at the CPU from behind like shown in the picture Stick...

Страница 20: ...PU gray connectors with CageClamp technology are used You may connect wires with a cross section of 0 08 mm 2 to 2 5 mm2 You can use flexible wires without end case as well as stiff wires You fix the...

Страница 21: ...ep by step from top view For cabling you push the locking vertical to the inside with a suiting screwdriver and hold the screwdriver in this position Insert the deisolated wire into the round opening...

Страница 22: ...t connector on the module until it locks In this position the front connector juts out of the module and has no contact yet Deisolate your wires If needed use core end cases Thread the included cable...

Страница 23: ...se key at the front connector on the upper side of the module and at the same time push the front connector into the module until it locks Bolt the fixing screw of the front connector Now the front co...

Страница 24: ...ut interferencing the environment All System 300V components are developed for the deployment in hard industrial environments and fulfill high demands on the EMC Nevertheless you should project an EMC...

Страница 25: ...log lines must be laid isolated When transmitting signals with small amplitudes the one sided laying of the isolation may be favorable Lay the line isolation extensively on a isolation protected earth...

Страница 26: ...lation one sided Then you only achieve the absorption of the lower frequencies A one sided isolation connection may be convenient if the conduction of a potential compensating line is not possible ana...

Страница 27: ...ture and the operation of the VIPA digital input modules The following text describes System overview of digital input modules Properties Structure Circuit and schematic diagram Technical data Topic P...

Страница 28: ...IPA 321 1BH01 DI 16xDC24V X 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 SM321 VIPA 321 1BL00 DI 32xDC24V X 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 SM321 VIPA 321 1FH00 DI 16xAC120 230V X 2 3 4 0 1 2 3 4 5 6 7...

Страница 29: ...ximate switches Status monitoring of the channels via LED 3 4 1 2 2 3 4 5 6 7 8 9 12 13 14 15 16 17 18 19 20 M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 9...

Страница 30: ...ents Potentials Isolation between channels and backplane bus yes Isolation tested with DC 500V Current consumption from the backplane bus 25mA Power dissipation of the module 3 5W Status Interrupts Di...

Страница 31: ...13 14 15 16 17 18 19 20 1M 22 23 24 25 26 27 28 29 32 33 34 35 36 37 38 39 40 2M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 9 12 19 20 21 22 29 32 39 40 As...

Страница 32: ...c module Number of inputs 32 Programming specifications Input data 4Byte Voltages Currents Potentials Isolation between channels and backplane bus yes between channels yes in groups of 16 Isolation te...

Страница 33: ...g strip contact bar flap opened with inner label Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Neutral conductor Input I 0 0 Input I 0 1 Input I 0 2 Input I 0 3 Input I 0 4 Input I...

Страница 34: ...vertical configuration up to 40 C 16 Isolation between channels and backplane bus yes between the channels yes in groups of 4 Permitted potential difference between Minternal and the inputs AC 230V b...

Страница 35: ...describes System overview of digital output modules Properties Structure Circuit and schematic diagram Technical data Topic Page Chapter 4 Digital Output Modules 4 1 System overview 4 2 322 1BF01 DO...

Страница 36: ...2A VIPA 322 1BH41 X 2 3 4 1L 0 1 2 3 4 5 6 7 F 2L 0 1 2 3 4 5 6 7 F SM322 DO 16xDC24V 0 5A VIPA 322 1BH60 X 2 3 4 L 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 F SM322 A 0 1 A 0 1 0 1 DO 32xDC24V 1A VIPA 322 1BL...

Страница 37: ...M322 1 2 3 4 5 6 7 SF 2A Type Order No Page DO 8xAC 120 230V 2A VIPA 322 5FF00 4 16 DO 16xRELAIS VIPA 322 1HH00 X 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 SM322 Type Order No Page DO 16xRelay VIPA 322 1H...

Страница 38: ...nels via LED 3 4 1 2 1 2 3 4 5 6 7 8 9 10 1L 1M 11 12 13 14 15 16 17 18 19 20 2L 2M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 3 5 7 9 10 11 13 15 17 19 20 As...

Страница 39: ...V Current consumption from the backplane bus 65mA from the load voltage L without load 68mA Power dissipation of the module 7 5W Status Interrupts Diagnostics Status display green LED per channel Grou...

Страница 40: ...s monitoring of the channels via LED 3 4 1 2 1 2 3 4 5 6 7 8 9 10 1L 1M 11 12 13 14 15 16 17 18 19 20 2L 2M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 9 10...

Страница 41: ...els and backplane bus yes between the channels in groups of yes 8 Isolation tested with DC 500V Current consumption from the backplane bus 110mA from the load voltage L without load 30mA Power dissipa...

Страница 42: ...s monitoring of the channels via LED 3 4 1 2 1 2 3 4 5 6 7 8 9 10 1L 1M 11 12 13 14 15 16 17 18 19 20 2L 2M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 9 10...

Страница 43: ...t per group 8A Isolation between channels and backplane bus yes between the channels in groups of yes 8 Isolation tested with DC 500V Current consumption from the backplane bus 110mA from the load vol...

Страница 44: ...rd supply voltage DC 24V output voltage 0 5A LEDs for supply voltage and error messages Status monitoring of the channels via LED 4 5 1 2 1 2 3 4 5 6 7 8 9 10 L 11 12 13 14 15 16 17 18 19 20 M 3 1 2 3...

Страница 45: ...osition of the according channel via the input word For this is valid triple switch input word Description 1 0 A I x 0 Manual 1 output channel always activated 1 0 A I x 0 Manual 0 output channel alwa...

Страница 46: ...ane bus 100mA from the load voltage L without load 140mA Power dissipation of the module 6W Status Interrupts Diagnostics Status display green LED per channel Group error display red F LED Data for se...

Страница 47: ...It has 16 channels and their status is monitored via LEDs 32 outputs potential separated to the back panel bus Supply voltage DC 24V Output voltage 1A per channel Useable for magnetic valve and DC co...

Страница 48: ...VIPA 322 1BL00 X 2 3 4 1 3L 0 1 2 3 4 5 6 7 1 3 F 2 4L 0 1 2 3 4 5 6 7 2 4 F SM322 LED 1 3L 2 4L 0 7 1 3F 2 4F Description LED green supply voltage is on LEDs green Q 0 0 to Q 3 7 As soon as an output...

Страница 49: ...imensions and weight Dimensions WxHxD 40x125x120mm Weight 200g Data for specific module Number of outputs 32 Programming specifications Output data 4Byte Voltages Currents Potentials Rated load voltag...

Страница 50: ...status is monitored via LEDs 8 outputs isolated between the channels and to the back plane bus Rated load voltage AC 120 230V Output current per channel 2A Suitable for AC solenoid valves contactors...

Страница 51: ...IPA 322 5FF00 X 2 3 4 0 SM322 1 2 3 4 5 6 7 SF 2A LED SF 0 7 Description LED red Group errror LED error if module is not supplied with parameters by the CPU LED green Q 0 0 to Q 0 7 As soon as an outp...

Страница 52: ...the digital output modules of VIPA are to be projected as digital output modules of Siemens in accordance with the following rules VIPA 322 5FF00 to be configured as 6ES7 322 5FF00 0AB0 The digital ou...

Страница 53: ...00h 1 Substitute value Bit 0 Substitute value 1 on channel 0 Bit 1 Substitute value 1 on channel 1 Bit 2 Substitute value 1 on channel 2 Bit 3 Substitute value 1 on channel 3 Bit 4 Substitute value 1...

Страница 54: ...onsumption from the backplane bus max 100mA from the load voltage L1 without load max 2mA Power dissipation of the module typ 8 6W Status Interrupts Diagnostics Status display green LED per Channel Di...

Страница 55: ...voltage AC 230V DC 30V Maximal contact rating per channel 5A useable for small motors lamps magnetic valve and DC contacter Activity LED per channel 3 4 1 2 1 2 3 4 5 6 7 8 9 10 1L1 L DC 24V 11 12 13...

Страница 56: ...agram Schematic diagram 1 2 3 4 5 6 7 8 9 10 1L1 L DC 24V 11 12 13 14 15 16 17 18 19 20 2L1 M DC 24V Mintern backplane bus Optocoupler LED Relay output module Note When using inductive load please tak...

Страница 57: ...the outputs per group 8A Isolation between channels and backplane bus yes between the channels yes in groups of 8 Isolation tested with DC 500V Current consumption from the backplane bus 80mA from po...

Страница 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...

Страница 59: ...digital in output modules The following text describes System overview of digital input output modules Properties Structure Circuit and schematic diagram Technical data Topic Page Chapter 5 Digital In...

Страница 60: ...4 5 6 7 F SM323 0 0 1 1 IN OUT IN OUT Type Order No Page DIO 16xDC 24V 1A VIPA 323 1BH00 5 3 DI 8xDC 24V DO 8xDC 24V 1A VIPA 323 1BH01 5 5 DI 16xDC 24V DO 16xDC 24V 1A VIPA 323 1BL00 5 7 Security hin...

Страница 61: ...oad overheat or short circuit Activity monitoring of the channels via LED 3 4 1 2 1 2 3 4 5 6 7 8 9 10 L M 11 12 13 14 15 16 17 18 19 20 L M 1 2 3 4 LEDs flap with labeling strip contact bar flap open...

Страница 62: ...ith DC 500V Current consumption from the backplane bus 130mA from load voltage L without load 30mA Power dissipation of the module 4W Status Interrupts Diagnostics Status display green LED per channel...

Страница 63: ...e channels via LED 3 4 1 2 2 3 4 5 6 7 8 9 10 1M 11 12 13 14 15 16 17 18 19 20 2L 2M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 9 10 11 12 19 20 Assignment...

Страница 64: ...backplane bus 70mA from load voltage L without load 15mA Power dissipation of the module 4W Status Interrupts Diagnostics Status display green LED per channel Group error display red F LED Data for se...

Страница 65: ...L 2M 31 32 33 34 35 36 37 38 39 40 3L 3M 1 2 3 4 LEDs flap with labeling strip contact bar flap opened with inner label Pin 1 2 19 20 21 31 22 39 30 40 Assignment Not used Input I 0 0 Input I 1 7 Grou...

Страница 66: ...backplane bus 130mA from load voltage L without load 30mA Power dissipation of the module 5 8W Status Interrupts Diagnostics Status display green LED per channel Group error display red F LED Data for...

Страница 67: ...input modules Connection Parameterization Measuring ranges Technical Data Topic Page Chapter 6 Analog Input Modules 6 1 System overview 6 2 Safety consideration 6 2 Parameterization Basics 6 4 331 1KF...

Страница 68: ...I 2x12Bit U I R Thermo Pt Ni100 VIPA 331 7KB01 6 17 AI 8x12Bit U I R Thermo Pt Ni100 VIPA 331 7KF01 6 17 Security hint Attention Please regard that the modules described here do not have hardware prec...

Страница 69: ...rt circuits at non used inputs by connecting the positive contact with the channel ground of the according channel The analog input modules from VIPA do not have any measuring range plug The modules a...

Страница 70: ...ed in sequence starting with slot 4 Here the analog input modules of VIPA are to be projected as analog input modules of Siemens VIPA 331 1KF01 to be configured as 6ES7 331 1KF01 0AB0 VIPA 331 7KF01 t...

Страница 71: ...pe 5 Mode Channel 6 7 Bit 3 0 Measuring range Bit 7 4 Measuring type 6 7 Upper limit value Channel 0 8 9 Lower limit value Channel 0 10 11 Upper limit value Channel 2 Var rec1 array 0 13 of BYTE retva...

Страница 72: ...ing Here the corresponding binary code of the measuring type may be found Within the measuring types there are the measuring ranges for which a binary measuring range code is to be specified in each c...

Страница 73: ...8 inputs Measuring value resolution 12Bit sign Isolated to the backplane bus After Power ON the module has the following default configuration These can be changed by hardware configuration measuring...

Страница 74: ...nel 3 I channel 3 S channel 3 M channel 3 M channel 3 U channel 4 I channel 4 S channel 4 M channel 4 M channel 4 U channel 5 I channel 5 S channel 5 M channel 5 M channel 5 U channel 6 I channel 6 S...

Страница 75: ...tances and resistance thermometers a connection of the M connections is not required Temporarily not used inputs with activated channel must be connected with the concerning ground When not used chann...

Страница 76: ...oose the according module and drag drop it to the concerning slot in the hardware configurator Via double click on the wanted module in the hardware configurator you open the concerning parameter wind...

Страница 77: ...3 0 Measuring range Bit 7 4 Measuring type 7 Mode channel 5 Bit 3 0 Measuring range Bit 7 4 Measuring type 8 Mode channel 6 Bit 3 0 Measuring range Bit 7 4 Measuring type 9 Mode channel 7 Bit 3 0 Meas...

Страница 78: ...ive region 32511 1 5V Nominal range 0 27648 0 296V End Underdrive region 4864 0111b 0 10V Connection 1 11 759V End Overdrive region 32511 0 10V Nominal range 0 27648 1 759V End Underdrive region 4864...

Страница 79: ...Standard 250 0 60 0 2500 600 482 0 76 0 4820 760 523 2 213 2 5232 2132 Nominal range 0011b 105 0 1050 157 0 1570 168 2 1682 End Under drive region Meas range C 0 01 C digit Unit dec F 0 01 F digit Un...

Страница 80: ...resistance thermometer and resistance measurement 0 600 0 83mA resistance measurement 0 6k 0 25mA Isolation between channels and backplane bus yes between the channels no Permitted potential differenc...

Страница 81: ...tional limit in the entire temperature range with reference to the input range Measuring range Tolerance Voltage input 50mV 500mV 1V 0 5 5V 1 5V 10V 0 10V 0 6 Current input 20mA 0 20mA 4 20mA 0 5 Resi...

Страница 82: ...tion limit max 30V Maximum input voltage for voltage input M destruction limit max 12V 30V for max 1s Maximum input current for current input L destruction limit 40mA Connection of the sensors for mea...

Страница 83: ...ace during software project engineering Plugging and unplugging during operation is not supported Voltage and current sensors thermocouples resistors and resistance thermometers may be connected 8 inp...

Страница 84: ...LED red Group error ON as soon as a diagnostic entry is present respectively during missing external voltage supply LED red Channel error ON together with SF if error respectively overflow measuring...

Страница 85: ...e measurand transducer transduces the measurand value into a current Please regard that the 4wire measurand transducers have to be provided external The following picture illustrates the connection of...

Страница 86: ...on point via compensating lines The compensating lines have the same material as the wires of the thermocouple The leads are out of copper In this case you should use the external compensation Please...

Страница 87: ...e connections M and M ADU Lo gic Bus M I M IC C M I M IC C 4wire connection 3wire connection 2wire connection M M IC IC M measuring line positive M measuring line negative IC constant current line pos...

Страница 88: ...ce exclusively at run time ADU M M M M Lo gik COMP COMP M M Bus IC IC Pt100 Copper cables M measuring line positive M measuring line negative IC constant current line positive IC constant current line...

Страница 89: ...The not used low byte bits are set to 0 Resolution Analog value High Byte Low Byte Bit number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Value SG 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 14Bit sig...

Страница 90: ...no 6ES7 331 7KB01 2x12Bit and 6ES7 331 7KF01 8x12Bit can be found at SIMATIC 300 SM 300 AI 300 Choose the according module and drag drop this module to the concerning slot in the hardware configurator...

Страница 91: ...ease Bit 7 Process interrupt release 00h 1 Interference frequency suppression Bit 0 1 Channel 0 1 Bit 2 3 Channel 2 3 Bit 4 5 Channel 4 5 Bit 6 7 Channel 6 7 AAh 2 Mode Channel 0 1 Bit 3 0 Measuring r...

Страница 92: ...ion 32512 0110b 10V 11 758V End Overdrive region 32511 10 10V Nominal range 27648 27648 11 759V End Underdrive region 32512 1001b 1 5V 5 703V End Overdrive region 32511 1 5V Nominal range 0 27648 0 29...

Страница 93: ...derdrive region 2430 0 1 C digit 0010b Pt100 Climate 155 C End Overdrive region 15500 120 130 C Nominal range 12000 13000 145 C End Underdrive region 14500 0 01 C digit 0000b Pt 100 reference junction...

Страница 94: ...n 2700 0111b 1 Type R PtRh Pt 2019 End Overdrive region 20190 50 1769 Nominal range 500 17690 170 End Underdrive region 1700 0011b 1 Type S PtRh Pt 2019 End Overdrive region 20190 50 1769 Nominal rang...

Страница 95: ...ation and works off the OB 82 For more detailed diagnostic information you may call the SFC 51 res SFC 59 in the OB 82 The diagnostic data is consistent until you leave the OB 82 When an error occurs...

Страница 96: ...ostic data are consistent until leaving the OB 82 As soon as you have activated the diagnostic interrupt release record set 0 is transferred to the superordinated system in cause of an error The recor...

Страница 97: ...Number of diagnostic bits that the module throws per channel 08h 6 Bit 7 0 Number of similar channels of a module 04h 7 Bit 0 Channel error Channel 0 Bit 7 Channel error Channel 7 00h 8 Bit 0 Project...

Страница 98: ...suring range 4 20mA 1 5V sensor connection polarity inversion wrong measuring range other measuring ranges wrong measuring range Check connections Parameterize another measuring range Parameterize ano...

Страница 99: ...define how your CPU should react at a process interrupt As soon as a measuring value is out of the range defined in the parameterization a processes interrupt is initialized if this option is release...

Страница 100: ...ecord set 0 of Byte 3 for process interrupt lost After having processed the OB 82 the CPU jumps back to OB 40 The behavior of the analog input module depends on the location of the measuring value ins...

Страница 101: ...entials Rated supply voltage of electronics L DC 24V Reverse polarity protection yes Power supply of the transmitters Supply current max 30mA per channel Short circuit proof yes Constant current for r...

Страница 102: ...e Suppression of interference limits error Noises suppression for f n x f1 1 f1 interference frequency n 1 2 Common mode interference UCM 3V 70dB Series mode noise peak value of noise nominal value of...

Страница 103: ...pts Diagnostics Interrupts parameterizable Channel 0 and 2 parameterizable Channel 0 Process interrupt when limit has been exceeded parameterizable Channel 0 and 2 parameterizable Channel 0 Diagnostic...

Страница 104: ...ameterizable internal temperature compensation possible external temperature compensation with compensating box possible Compensation for 0 C comparison point temperature possible Technical unit for t...

Страница 105: ...xt describes System overview Safety instructions Connection possibilities Parameterization and diagnostics Hardware description Technical data Topic Page Chapter 7 Analog Output Modules 7 1 System ove...

Страница 106: ...12Bit I for manual operation VIPA 332 5HD50 7 18 AO 4x12Bit U for manual operation VIPA 332 5HD60 7 18 Security hint Attention Please regard that the modules VIPA 332 5Hx01 do not have hardware precau...

Страница 107: ...number 332 5Hx01 are set to voltage output 10V The interrupt output of every module is deactivated Every module described here has diagnostic functions Depending on the module the following errors ma...

Страница 108: ...achieve a high exactness at the load The sensor lines S X and S X are directly connected to the load Thus the voltage may be measured and adjusted directly at the load Interference or voltage losses...

Страница 109: ...ut values at the same nominal range The resolution depends on the used module as follows Analog value High byte Low byte Bit number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Resolution SG Analog value wor...

Страница 110: ...ted as analog output modules of Siemens in accordance with the following rules VIPA 332 5HD01 to be configured as 6ES7 332 5HD01 0AB0 VIPA 332 5HDx0 VIPA 332 5HB01 to be configured as 6ES7 332 5HB01 0...

Страница 111: ...Channel 3 00h 00h 00h 2 Mode Channel 0 Bit 3 0 Output range Bit 7 4 Output type 19h 10V 23h 4 20mA 18h 0 10V 3 Mode Channel 1 Bit 3 0 Output range Bit 4 7 Output type 19h 10V 23h 4 20mA 18h 0 10V 4 M...

Страница 112: ...range coding 4 3 The corresponding codes can be found in the following table Within the output types the output ranges are specified for which a binary output range code is to be specified in each ca...

Страница 113: ...rks on the OB 82 For more detailed diagnostic information you may call the SFC 51 res SFC 59 in the OB 82 The diagnostic data is consistent until you leave the OB 82 When an error occurs and after err...

Страница 114: ...request detailed diagnostic information by means of the SFCs 51 and 59 and react to it After the working off of the OB 82 the processing of the user application is continued The diagnostic data are co...

Страница 115: ...Channel specific error Channel 0 Bit 0 Project engineering Parameterization error Bit 1 2 reserved Bit 3 Short circuit after M Bit 4 Wire break Bit 7 5 reserved Channel specific error Channel 0 Bit 0...

Страница 116: ...l load voltage missing Load voltage L of the module is missing Proof connections L and M Proof power supply Project engineering Parameterization error Wrong parameters have been transferred to the mod...

Страница 117: ...mA or 0 20mA parameterizable diagnostics and diagnostics interrupt isolated between backplane bus and load voltage After Power ON the modules have the following default settings Output range 10V for a...

Страница 118: ...LED green the according channel is activated LED red Error channel 0 3 Note Please regard that you must not connect the S Pin at current output Due to the 2 channels of the module the channels CH2 an...

Страница 119: ...arity protection yes Isolation between channels backplane bus yes between channels Power supply of the electronics yes between channels no between channels load voltage L yes Permitted potential diffe...

Страница 120: ...Current outputs 4 20mA 0 5 1 0 20mA 0 4 1 20V 0 2 2 Temperature error with reference to the output range 0 01 K Linearity error with reference to the output range 0 1 Repeatability in steady state at...

Страница 121: ...at voltage outputs min 1k capacitive load max 1 F at current outputs max 500 inductive load max 10mH Voltage output Short circuit protection yes Short circuit current 30mA Current output No load opera...

Страница 122: ...32 5HD60 voltage output 0 10V deactivated usable for actuators with an input of 4 20mA VIPA 332 5HD50 usable for actuators with an input of 0 10V VIPA 332 5HD60 parameterizable diagnostics and diagnos...

Страница 123: ...18 19 20 Circuit diagram 1 2 3 4 5 6 7 8 9 10 L DC 24V 11 12 13 14 15 16 17 18 19 20 M Q2 M2 CH0 CH1 CH2 CH3 Q0 M0 Q1 M1 Q3 M3 SM332 AO 4x12Bit L H A H A H A H A LED L Description LED green supply vo...

Страница 124: ...If the potentiometer is turned in the clockwise direction beyond the max position then the overdrive region is reached Hardware conditionally an exact marking of the ranges is not possible As soon as...

Страница 125: ...potential difference between MANA and MINTERNAL UISO DC 75V AC 60V Isolation tested with DC 500V Current consumption from the backplane bus 80mA from power supply L no load 130mA Power dissipation of...

Страница 126: ...y LED green Diagnostic information readable possible Substitute value can be applied yes Data for selecting an actuator Output range rated values Voltage 0 10V Current 4 20mA Load resistance in the no...

Страница 127: ...8 7 6 during run time 4 19 7 7 Replacement value 7 8 Resolution 7 5 Security hint 7 2 Signal lines 7 3 substitute a value 4 19 System overview 7 2 Trouble shooting 7 12 Value representation 7 5 D Digi...

Страница 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...

Отзывы: