Manual VIPA System 300V
Chapter 7 Analog Output Modules
HB130E - SM - Rev. 07/44
7-7
If the module gets parameters, which are not supported by the module, for
example a current module is to be configured as a voltage module, these
parameters are interpreted as wrong parameters and an error is initialized.
At the parameterization, 16Byte long parameter area is set in the record
sets 0 and 1. Deploying the SFCs 55, 56 and 57, you may alter parameters
during run time and transfer them to the module. The following tables show
the structure of the parameters in record set 0 and 1:
Record set 0 (Byte 0 to 1):
Byte
Bit 7 ... Bit 0
Default
0
Sum diagnosis bit coded
Bit 0: Channel 0
Bit 1: Channel 1
Bit 2: Channel 2
Bit 3: Channel 3
Bit 7 ... 4: reserved
00h
1 reserved
00h
Record set 1 (Byte 0 to 13):
Default
Byte
Bit 7 ... Bit 0
332-5Hx01 332-5HD50 332-5HD60
0
Bit 5 ... 0: reserved
Bit 6: Diagnostic interrupt release
Bit 7: reserved
00h 00h 00h
1
Reaction at CPU-STOP
Bit 0: Channel 0
Bit 1: Channel 1
Bit 2: Channel 2
Bit 3: Channel 3
00h 00h 00h
2
Mode Channel 0
Bit 3 ... 0: Output range
Bit 7 ... 4: Output type
19h
(+/-10V)
23h
(4...20mA)
18h
(0...10V)
3
Mode Channel 1
Bit 3 ... 0: Output range
Bit 4 ... 7: Output type
19h
(+/-10V)
23h
(4...20mA)
18h
(0...10V)
4
Mode Channel 2
Bit 3 ... 0: Output range
Bit 7 ... 4: Output type
19h
(+/-10V)
23h
(4...20mA)
18h
(0...10V)
5
Mode Channel 3
Bit 3 ... 0: Output range
Bit 7 ... 4: Output type
19h
(+/-10V)
23h
(4...20mA)
18h
(0...10V)
6, 7
Replacement value Channel 0
0000h
0000h
0000h
8, 9
Replacement value Channel 1
0000h
0000h
0000h
10, 11 Replacement value Channel 2
0000h
0000h
0000h
12, 13 Replacement value Channel 3
0000h
0000h
0000h
Note!
With setting the mode parameter to 00h the according channel is
deactivated. To switch at not symmetric output range the current
respectively the voltage output to 0 value at CPU STOP, the following
replacement values should be used:
output range 1...5V:
0V
↔
-6912dez = E500h
output range 4...20mA:
0mA
↔
-6912dez = E500h
Parameterization
during run time
by means of
SFCs
Parameters
Record set 0
(not parameterizable
via SFC)
Parameters
Record set 1
The according
coding of
output type
and output
range can be
found at the
following page!
0: Switch output current and voltage
free res. set replacement value
1: hold last value
Содержание HB130E SM
Страница 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Страница 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Страница 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Страница 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...