Chapter 7 Analog Output Modules
Manual VIPA System 300V
7-10
HB130E - SM - Rev. 07/44
The diagnostics data is stored in the record sets 0 and 1 of the system data
area.
As soon as you have activated the diagnostic interrupt release of the
parameter area (record set 1, Byte 0), on error
record set 0
of the
diagnostics data is transferred to the superordinated system.
For extended diagnosis during run time, you may also evaluate the
Record
set 1
via the SFCs 51 and 59.
At a diagnostics event the CPU interrupts the user program and branches
into OB 82. This OB allows you via according programming to request
detailed diagnostic information by means of the SFCs 51 and 59 and react
to it.
After the working off of the OB 82, the processing of the user application is
continued. The diagnostic data are consistent until leaving the OB 82.
The
record set 0
has a fixed content. The content of
record set 0
may be
monitored in plain text in the diagnosis window of the CPU.
Byte
Bit 7 ... Bit 0
Default
0
Bit 0: Error in module
Bit 1: reserved
Bit 2: External error
Bit 3: Channel error
Bit 4: external voltage supply missing
Bit 5, 6: reserved
Bit 7: Wrong parameter in module
00h
1
Bit 3 ... 0: Module class
0101
Analog
module
Bit 4: Channel information present
15h
2
Bit 0, 1 reserved
Bit 2: Operating status
0: RUN
1:
STOP
Bit 7 ... 4: reserved
00h
3 not
used
00h
Diagnostics data
Evaluate
diagnosis
Diagnosis
Record set 0
Содержание HB130E SM
Страница 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Страница 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Страница 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Страница 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...