Manual VIPA System 300V
Chapter 6 Analog Input Modules
HB130E - SM - Rev. 07/44
6-37
... continue
... Suppression of interference, limits error
VIPA 331-7KF01
VIPA 331-7KB01
- Resistance thermometer
Pt100 Standard, Ni100
±0.5%
Pt100
Climate
±0.6%
- Thermocouple
Type J, K, N, L, E
±0.7%
Type
T
±1.1%
Type S, B, C, R
(see note at the end of the table)
Temperature error
(with reference to the input range)
±0.005%/K
Linearity error
(with reference to the input range)
±0.02%
Repeatability (in steady state at 25°C, with
reference to the input range)
±0.05%
Temperature error of internal compensation
±1.5%
Status, Interrupts, Diagnostics
Interrupts parameterizable
(Channel 0 and 2)
parameterizable
(Channel 0)
- Process interrupt when limit has been
exceeded
parameterizable
(Channel 0 and 2)
parameterizable
(Channel 0)
- Diagnostic interrupt
parameterizable
Diagnostic functions
- Group error display
red LED (SF)
red LED (F0...F7)
red LED (F0...F1)
- Diagnostics information read-out
possible
Data for selecting a sensor
Input range
Input resistance
-
Voltage
±
80mV,
±
250mV
10M
Ω
±
500mV,
±
1V
10M
Ω
±
2.5V,
±
5V
100k
Ω
1 ... 5V,
±
10V
100k
Ω
-
Current
±
3.2mA,
±
10mA,
±
20mA
85
Ω
0 ... 20mA, 4 ... 20mA
85
Ω
-
Resistors
0 ...150
Ω,
300
Ω,
600
Ω
10M
Ω
- Resistance thermometer
Pt100, NI100
10M
Ω
- Thermocouples
Type J, K, N, L, E, T,
S, B, C, R
10M
Ω
Maximum input voltage for voltage
input (destruction limit)
max. 20V
Maximum input current for current
input L+ (destruction limit)
max. 40mA
continued ...
Содержание HB130E SM
Страница 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Страница 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Страница 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Страница 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...