Chapter 4 Deployment of the CPU 21x-2BT10 with TCP/IP
Manual VIPA CPU 21x
4-44
HB103E - Rev. 05/45
For every READ and WRITE the CP generates PLC header for request
and acknowledgment messages. Normally the length of these headers is
16Bytes and have the following structure:
Request telegram
Remote Station
Acknowledgement telegram CP
System ID
="S5"
(Word)
System ID
="S5"
(Word)
Length.Header =10h
(Byte) Length.Header =10h
(Byte)
ID OP-Code
=01h
(Byte)
ID OP-Code
=01h
(Byte)
Length OP-Code
=03h
(Byte)
Length OP-Code
=03h
(Byte)
OP-Code =03h
(Byte)
OP-Code =04h
(Byte)
ORG block
=03h
(Byte)
Ackn. block
=0Fh
(Byte)
Length ORG block
=08h
(Byte)
Length Ack. block
=03h
(Byte)
ORG identifier*
(Byte)
Error no.
(Byte)
ERW identifier
(Byte)
Empty block
=FFh
(Byte)
Start address
(Word)
Length empty block =07h
(Byte)
Length
(Word)
5 empty bytes attached
Empty block
=FFh
(Byte)
Length empty block =02h
(Byte)
Data up to 64kByte (only if error no.=0)
Request telegram
Remote Station
Acknowledgement telegram CP
System ID
="S5"
(Word)
System ID
="S5"
(Word)
Length.Header =10h
(Byte) Length.Header =10h
(Byte)
ID OP-Code
=01h
(Byte)
ID OP-Code
=01h
(Byte)
Length OP-Code
=03h
(Byte)
Length OP-Code
=03h
(Byte)
OP-Code =05h
(Byte)
OP-Code =06h
(Byte)
ORG block
=03h
(Byte)
Ackn. block
=0Fh
(Byte)
Length ORG block
=08h
(Byte)
Length Ackn. block =03h
(Byte)
ORG identifier*
(Byte)
Error no.
(Byte)
ERW identifier
(Byte)
Empty block
=FFh
(Byte)
Start address
(Word)
Length empty block =07h
(Byte)
Length
(Word)
5 empty bytes attached
Empty block
=FFh
(Byte)
Length empty block =02h
(Byte)
Data up to 64kByte (only if error
no.=0)
*) More details to the data area is to be found at "ORG-Format" above.
Note!
Please regard that in opposite to Siemens-S5 systems, the block
addressing of these CPUs takes the start address as byte number and the
length as number of words.
The following messages can be returned via
error no.
:
Error no. Message
00h
No error occurred
01h
The defined area cannot be read res. written
Structure of PLC-
Header
WRITE
FETCH
Messages of
error no.
Содержание CPU 21 Series
Страница 1: ...Manual VIPA CPU 21x Order No VIPA HB103E Rev 05 45 ...
Страница 2: ...Lerrzeichen ...
Страница 6: ...About this Manual Manual VIPA CPU 21x Subject to change to cater for technical progress ...
Страница 10: ...Contents Manual VIPA CPU 21x iv HB103E Rev 05 45 ...
Страница 30: ...Chapter 1 Principles Manual VIPA CPU 21x 1 18 HB103E Rev 05 45 ...
Страница 58: ...Chapter 2 Hardware description Manual VIPA CPU 21x 2 28 HB103E Rev 05 45 ...
Страница 80: ...Chapter 3 Deployment CPU 21x Manual VIPA CPU 21x 3 22 HB103E Rev 05 45 ...
Страница 178: ...Chapter 5 Deployment CPU 21x 2BT02 with H1 TCP IP Manual VIPA CPU 21x 5 48 HB103E Rev 05 45 ...