Chapter 4 Deployment of the CPU 21x-2BT10 with TCP/IP
Manual VIPA CPU 21x
4-20
HB103E - Rev. 05/45
For the assignment of the IP parameters such as IP address, Subnet mask
etc. you have the following possibilities:
•
Online using Siemens SIMATIC Manager via "Assign Ethernet Address"
(at least CP-Firmware 1.7.4)
•
with the help of a "minimum project" and transfer this via MMC or MPI
into the CPU. After a reboot of the CPU and after switching the PG/PC
interface to "TCP/IP... RFC1006" you may now configure your CPU
online via the CP.
Please regard this functionality is available with firmware version 1.7.4 and
up.
•
Start Siemens SIMATIC Manager
•
Switch to "TCP/IP... RFC1006" using
Options
>
Set PG/PC interface
.
•
The dialog for initialization of a station opens by
PLC
>
Assign Ethernet-
Address
.
•
To get the stations and their MAC address use the [Browse] button or
type in the MAC Address. The Mac address can be found at a label at
the side of the CPU.
•
Choose if necessary the known MAC address of the list of found
stations.
•
Either type in the IP configuration like IP address, subnet mask and
gateway. Or your station is automatically provided with IP parameters by
means of a DHCP server. Depending of the chosen option the DHCP
server is to be supplied with MAC address, equipment name or client ID.
The client ID is a numerical order of max. 63 characters. The following
characters are allowed: "hyphen", 0-9, a-z, A-Z
•
Confirm with [Assign ...]
Directly after the assignment the CP is online reachable using the set IP
parameters.
•
Start Siemens SIMATIC Manager with new project.
•
Place a new System 300 station with
Insert
>
Station
>
SIMATIC 300
station
•
Activate the station "SIMATIC 300" and open the hardware configurator
by clicking on "Hardware".
•
Configure a rack (SIMATIC 300 \ Rack-300 \ Profile rail).
•
Engineer in deputy of your CPU 21xNET the Siemens CPU 315-2DP
with the order no. 6ES7 315-2AF03-0AB0 V1.2. which is to be found at
SIMATIC 300 \ CPU 300 \ CPU 315-2 DP \ 6ES7 315-2AF03-0AB0. If
needed, parameterize the CPU 315-2DP.
•
Configure in deputy of your CP the
CP 343-1 (343-1EX11)
from
Siemens at slot 4, to be found at SIMATIC 300 / CP 300 / Industrial
Ethernet / CP 343-1.
•
Set IP address, subnet mask and gateway at CP properties. This is the
end of the
Minimal project
. After the
Minimal project
is transferred to
CPU, the CPU can be accesses by means of IP address and Subnet
mask of the project.
Assign IP
parameters
Address
assignment with
"Assign Ethernet
Address"
Address
assignment with
minimal project
Содержание CPU 21 Series
Страница 1: ...Manual VIPA CPU 21x Order No VIPA HB103E Rev 05 45 ...
Страница 2: ...Lerrzeichen ...
Страница 6: ...About this Manual Manual VIPA CPU 21x Subject to change to cater for technical progress ...
Страница 10: ...Contents Manual VIPA CPU 21x iv HB103E Rev 05 45 ...
Страница 30: ...Chapter 1 Principles Manual VIPA CPU 21x 1 18 HB103E Rev 05 45 ...
Страница 58: ...Chapter 2 Hardware description Manual VIPA CPU 21x 2 28 HB103E Rev 05 45 ...
Страница 80: ...Chapter 3 Deployment CPU 21x Manual VIPA CPU 21x 3 22 HB103E Rev 05 45 ...
Страница 178: ...Chapter 5 Deployment CPU 21x 2BT02 with H1 TCP IP Manual VIPA CPU 21x 5 48 HB103E Rev 05 45 ...