User Manual
Arctic Substation Gateway
Firmware Version 2.4.x
41
Document Version 1
Table 36: IEC-104 ASDU common address length
IEC-104 ASDU common address length
Type
Field length
Units
Bytes
Value range
1-3
Note
The IEC-104 standard defines value 2.
Info object address length (IEC-104)
This defines the length of IEC-104 Information object address ASDU header
field in bytes.
Table 37: IEC-104 ASDU information object address length
IEC-104 ASDU information object address length
Type
Field length
Units
Bytes
Value range
1-3
Note
The IEC-104 standard defines value 3.
7.5
IEC-101 settings
The IEC-101 settings define the properties of IEC-101 link layer and
application layer parameters as described in the IEC 60870-5-101 standard.
The IEC-101 communication is carried out between the Arctic and a IEC-101
slave.
Figure 30. IEC-101 Settings
Slave link address (IEC-101)
Table 38: IEC-101 slave link address
IEC-101 slave link address
Type
Link address