INSTALLATION INSTRUCTIONS 
Hydrosense ID Addressable Water Detection System 

 

 

Document Part No. 3500039 Issue:01 

Page | 7 of 32 

 

 

4.1 Installation 

The installation of the panel should be carried out by qualified personnel only. The electronic components within 

the panel are vulnerable to physical damage and damage by electrostatic discharges.   

It  is  advisable  to  wear  a  wrist  strap  designed  to  prevent  the  build-up  of  static  charges  within  the 

body, before handling any electronic circuit boards. 

Never  insert  or  remove  boards  or  components  with  the  power  on.  To  avoid  this  hazard  a  Mains 

Isolator Switch should be installed.

 

Mounting the Cabinet 

The site chosen for the location of the panel should be clean and dry and not subject to shock or vibration. The 
temperature should be in the range -5° to +35° C, the humidity should not exceed 95%. 

 

 

Open  the  outer  cover  using  the  key  provided. 

Unplug  the  power  terminal  block  from  the  left 
hand side of the circuit board, remove the two 

screws  holding  the  plate  in  position  and  then 
remove the complete circuit board and plate.  

Hold the assembly by gripping the metal plate 
only  and  try  to  avoid  touching  the  circuit 

board. 

Place  the  plate/circuit  board  assembly  and 

fixing  screws  in  a  safe  location  to  prevent 
accidental damage. 

The  outer  cover  can  be  removed  to  make 
fitting  more  manageable  by  removing  the  two 

pins holding it in position on the left hand side. 

 

 

 

 

 

Remove knockouts from the top and or back of 

the box in the positions at which cables will 
enter. 

 

When  surface  mounting  use  the  box  as  a 

template,  mark  the  position  of  the  top-fixing 
hole, ensuring that the wall is flat at the chosen 

location.  The  top  fixing  is  a  keyhole  slot  and 
fitting  a  screw  here  and  hanging  the  box  first 

will  assist  in  marking  the  remaining  fixing 
points. 

Screws  or  bolts  of  a  minimum  of  5  mm 
diameter  and  40  mm  long  must  be  used  to 

mount  the  enclosure  in  all  three  mounting 
positions. 

After  the  box  is  firmly  fixed,  remove  any 
knockout  blanks  and  dust  or  swarf  caused  by 

drilling and fixing the box. 

See  bezel  installation  instructions  if  Semi  or 

Deep recess mounting. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание hydrosense IDAP-S-2-230

Страница 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions Issue 01 October 2018 By www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...ring the Panel Autolearn Initial Startup 12 8 3 Configuring the Panel from PC 13 9 Facilities Menu 14 10 Detection circuits 15 10 1 Fitting additional Detection Circuit Loop Card IDAP LEC 16 11 Panel...

Страница 3: ...for Water Leak in Same Zone 23 16 1 14 Resound for Leak Detection in Other Zone 23 16 1 15 Hide Disablement Event for Active Delays 23 16 1 16 Delays Active on Initialisation 23 16 1 17 Ignore Global...

Страница 4: ...19 3 Current Consumption 30 19 4 Power Supply 30 19 5 Field Devices 30 19 6 Water Leak Alarm Fault Relay Ratings see also Section 12 30 19 7 Zones 30 19 8 Remote Control Inputs see also Section 16 30...

Страница 5: ...ub address 123 2 Three addresses from 800 available The sub addresses can be treated as if they were individual addresses i e each can be allocated to any zone given an individual address message and...

Страница 6: ...mA Maximum Ripple Voltage 1 5 0 3 Volts Battery Type Genesis E NP 7 12 7Ah 12V Battery Charge Voltage 27 6 VDC nominal temperature compensated Battery Charge Current 0 7 Amps Battery Fuse 20mm 3 15A...

Страница 7: ...screws holding the plate in position and then remove the complete circuit board and plate Hold the assembly by gripping the metal plate only and try to avoid touching the circuit board Place the plat...

Страница 8: ...of devices used and should be calculated for each installation Cabling for sounder circuits should be sized according to sounder load and cable length but 1 5mm2 should suffice in the majority of cas...

Страница 9: ...the mains terminal block to minimise the danger of them shorting to other parts of the equipment if they become disconnected The mains terminal block contains a F1 6A L250V fuse and must be replaced...

Страница 10: ...onnel and should not be operated by the user under any circumstances Opening the front cover also gives access to the PC Connection Port for programming If the processor stops running or re boots for...

Страница 11: ...s fuse that will rupture if excessive current is demanded from the battery by the control panel This fuse is labelled F4 and is located on the underside of the circuit board To replace the battery fus...

Страница 12: ...de switch located behind the aperture in the bottom right corner of the plate to the left position using a small screwdriver or similar tool Then press the internal Reset switch that can be seen throu...

Страница 13: ...to normal by re starting the panel by pressing the Reset switch located with the door open and to the right of the Fuse Fail LED 8 3 Configuring the Panel from PC To allow configuration from a PC it i...

Страница 14: ...acilities Menu A number of facilities are provided which can only be reached at Access Level 2 or 3 Access Level 2 can be reached by entering the correct password a 4 digit number and pressing the ent...

Страница 15: ...in the wiring all of the devices will still remain connected to the control panel In the case of a short circuit the short circuit isolators will isolate the faulty section of the wiring and the pane...

Страница 16: ...stallation The additional Loop Card mounts on the left hand side of the main board and fits into two connectors labelled X7 and X8 There are two mounting pillars on the main board to which the additio...

Страница 17: ...the sounders will operate at the end of the delay unless the panel is reset Activation of two or more devices producing a Water Leak action an input configured to override output delays will override...

Страница 18: ...se ID panel 14 1 16 Channel I O Board ID SIO 16 The 16 channel I O boards can be individually configured using the Loop Explorer PC LE2 configuration utility to modify its operation in response to Ala...

Страница 19: ...acts which default to Leak Detection and Fault actions The 4 way Zone Board is in effect a self contained 4 zone conventional control unit For full details of 4 way zone boards refer to manual 3500044...

Страница 20: ...he full 500 mA capability of this output for instance would require an additional 15 Ah of battery capacity Ideally use of the Aux 24V Output should be restricted to powering a limited number of addit...

Страница 21: ...em from the Aux 24V Output such as additional I O boards should be catered for by additional capacity using the same formula as above and adding the result to the calculated capacity required to maint...

Страница 22: ...nel is mounted The panel name can be up to 15 characters long 16 1 2 Panel Address Hydrosense ID panels should always be set to address 1 16 1 3 Protocol Control panels are supplied as Hydrosense comp...

Страница 23: ...brightness of the display when the panel is installed in darkened locations such as control rooms and ships bridges 16 1 12 Any 2 Devices to Bypass Delays Def Ring Mode Outputs Only When this option i...

Страница 24: ...es is the INPUT ACTION and the following describes how the control panel will respond to each of these As mentioned previously because this is fundamentally a Water Leak detection system 16 2 1 Water...

Страница 25: ...stored in the event log 16 2 9 Reset Action An input designated as Reset will not produce any visible effect at the control panel but will reproduce the action of the Reset Button on the panel i e re...

Страница 26: ...on continuously when any sound alarm input is operated This normally applies to sounders and would normally be accompanied by the Def Ring Mode and Silenceable attributes Note Any output on the Hydros...

Страница 27: ...nfiguring outputs with a combination of delays to some outputs and no delays to other outputs To start the stage two delay the Silence Alarm Acknowledge button must be pressed during the stage one del...

Страница 28: ...nly Inputs in the selected zone that are not configured as Water leak event type will not contribute to a Zonal Cause Effect Cause Effects can also be used to disable any Outputs or groups of Outputs...

Страница 29: ...ettings 18 1 Contrast Adjust The viewing angle contrast of the Hydrosense ID front panel display may be adjusted by turning the CONTRAST adjust potentiometer The contrast adjust potentiometer can be a...

Страница 30: ...250 mA in full alarm 19 4 Power Supply Supply Voltage 230 VAC nominal 10 15 Supply rating 3 Amps Battery Charger Charges up to 9 Ah sealed lead acid batteries with temperature compensation over the ra...

Страница 31: ...s start occurring from devices fitted at the other end of the loop Also excessive Loop Sounder Current will cause bad data faults to occur when the sounders are operated In general the user is unaware...

Отзывы: