background image

INSTALLATION INSTRUCTIONS 
Hydrosense ID Addressable Water Detection System 

 

 

Document Part No. 3500039 Issue:01 

Page | 22 of 32 

 

 

16. Programming via Loop Explorer PC (LE2) Configuration Utility 

Due to the use of the very latest microprocessor and memory technology, the Hydrosense ID Water Leak control 

Panel is an extremely powerful controller.  

As such, it can be programmed in an almost infinite number of ways, some of which will not give the visual and 

audible indications expected from a Water Detection system.  

Any  re-programming  from  the  factory  default  settings  must  therefore  be  carried  out  by  competent  systems 

engineers and thoroughly tested against the system plans before final commissioning. 

Although  the  Hydrosense  ID  is  very  powerful  and  can  be  programmed  to  perform  some  complex  tasks,  the 

principals adopted in the way that inputs and outputs are handled make it conceptually very simple. 

16.1. Panel Settings 

There  are  a  number  of  attributes  for  the  panel,  which  can  be  changed  using  the  configuration  programme  as 

shown below. 

 

16.1.1. Panel Name 

By default the panel name will be set to the panel 
type. “Hydrosense ID” 

 

The  panel  name  would  normally  describe  its 
location  such  as  the  name  of  the  building  or 

facility where the panel is mounted. 

The panel name can be up to 15 characters long. 

16.1.2. Panel Address 

Hydrosense  ID  panels  should  always  be  set  to 

address 1.

 

16.1.3. Protocol 

Control  panels  are  supplied  as  Hydrosense  
compatible  only. 

(Note:  System  only  works 

with  specific  devices  for  the  Hydrosense  ID 
system).

 

The  label  inside  the  control  panel  showing  the 
part  number  identifies  which  protocol  is  being 

used, it must start with a H 

 

 

 

16.1.4. Number of Loops 

Control panels are supplied with 1 or 2 detection loops fitted. The configuration file should be created with the 

same number of loops as the control panel for which it is destined. 

The repeater panel does NOT support any detection loops, and has its own communication protocol. This panel 

option may be selected when adding panels to the configuration only.

 

16.1.5. Default Ringing Mode 

The  default-ringing  mode  is  set  to  common  alarm.  In  this  mode,  any  Water  Leak  condition  will  operate  all 
sounders continuously. 

The mode can be changed to Zonal Alarm, which means that only sounders in the same zone as the signal that 
originated the alarm will operate. 

A third option of 2-stage alarm is also available which causes the sounders in the same zone as the signal that 

originated the alarm to operate continuously and sounders in all other zones to operate intermittently. 

16.1.5.1 – Marine Mode 

Function not applicable – Currently this feature is not used. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание hydrosense IDAP-S-2-230

Страница 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions Issue 01 October 2018 By www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...ring the Panel Autolearn Initial Startup 12 8 3 Configuring the Panel from PC 13 9 Facilities Menu 14 10 Detection circuits 15 10 1 Fitting additional Detection Circuit Loop Card IDAP LEC 16 11 Panel...

Страница 3: ...for Water Leak in Same Zone 23 16 1 14 Resound for Leak Detection in Other Zone 23 16 1 15 Hide Disablement Event for Active Delays 23 16 1 16 Delays Active on Initialisation 23 16 1 17 Ignore Global...

Страница 4: ...19 3 Current Consumption 30 19 4 Power Supply 30 19 5 Field Devices 30 19 6 Water Leak Alarm Fault Relay Ratings see also Section 12 30 19 7 Zones 30 19 8 Remote Control Inputs see also Section 16 30...

Страница 5: ...ub address 123 2 Three addresses from 800 available The sub addresses can be treated as if they were individual addresses i e each can be allocated to any zone given an individual address message and...

Страница 6: ...mA Maximum Ripple Voltage 1 5 0 3 Volts Battery Type Genesis E NP 7 12 7Ah 12V Battery Charge Voltage 27 6 VDC nominal temperature compensated Battery Charge Current 0 7 Amps Battery Fuse 20mm 3 15A...

Страница 7: ...screws holding the plate in position and then remove the complete circuit board and plate Hold the assembly by gripping the metal plate only and try to avoid touching the circuit board Place the plat...

Страница 8: ...of devices used and should be calculated for each installation Cabling for sounder circuits should be sized according to sounder load and cable length but 1 5mm2 should suffice in the majority of cas...

Страница 9: ...the mains terminal block to minimise the danger of them shorting to other parts of the equipment if they become disconnected The mains terminal block contains a F1 6A L250V fuse and must be replaced...

Страница 10: ...onnel and should not be operated by the user under any circumstances Opening the front cover also gives access to the PC Connection Port for programming If the processor stops running or re boots for...

Страница 11: ...s fuse that will rupture if excessive current is demanded from the battery by the control panel This fuse is labelled F4 and is located on the underside of the circuit board To replace the battery fus...

Страница 12: ...de switch located behind the aperture in the bottom right corner of the plate to the left position using a small screwdriver or similar tool Then press the internal Reset switch that can be seen throu...

Страница 13: ...to normal by re starting the panel by pressing the Reset switch located with the door open and to the right of the Fuse Fail LED 8 3 Configuring the Panel from PC To allow configuration from a PC it i...

Страница 14: ...acilities Menu A number of facilities are provided which can only be reached at Access Level 2 or 3 Access Level 2 can be reached by entering the correct password a 4 digit number and pressing the ent...

Страница 15: ...in the wiring all of the devices will still remain connected to the control panel In the case of a short circuit the short circuit isolators will isolate the faulty section of the wiring and the pane...

Страница 16: ...stallation The additional Loop Card mounts on the left hand side of the main board and fits into two connectors labelled X7 and X8 There are two mounting pillars on the main board to which the additio...

Страница 17: ...the sounders will operate at the end of the delay unless the panel is reset Activation of two or more devices producing a Water Leak action an input configured to override output delays will override...

Страница 18: ...se ID panel 14 1 16 Channel I O Board ID SIO 16 The 16 channel I O boards can be individually configured using the Loop Explorer PC LE2 configuration utility to modify its operation in response to Ala...

Страница 19: ...acts which default to Leak Detection and Fault actions The 4 way Zone Board is in effect a self contained 4 zone conventional control unit For full details of 4 way zone boards refer to manual 3500044...

Страница 20: ...he full 500 mA capability of this output for instance would require an additional 15 Ah of battery capacity Ideally use of the Aux 24V Output should be restricted to powering a limited number of addit...

Страница 21: ...em from the Aux 24V Output such as additional I O boards should be catered for by additional capacity using the same formula as above and adding the result to the calculated capacity required to maint...

Страница 22: ...nel is mounted The panel name can be up to 15 characters long 16 1 2 Panel Address Hydrosense ID panels should always be set to address 1 16 1 3 Protocol Control panels are supplied as Hydrosense comp...

Страница 23: ...brightness of the display when the panel is installed in darkened locations such as control rooms and ships bridges 16 1 12 Any 2 Devices to Bypass Delays Def Ring Mode Outputs Only When this option i...

Страница 24: ...es is the INPUT ACTION and the following describes how the control panel will respond to each of these As mentioned previously because this is fundamentally a Water Leak detection system 16 2 1 Water...

Страница 25: ...stored in the event log 16 2 9 Reset Action An input designated as Reset will not produce any visible effect at the control panel but will reproduce the action of the Reset Button on the panel i e re...

Страница 26: ...on continuously when any sound alarm input is operated This normally applies to sounders and would normally be accompanied by the Def Ring Mode and Silenceable attributes Note Any output on the Hydros...

Страница 27: ...nfiguring outputs with a combination of delays to some outputs and no delays to other outputs To start the stage two delay the Silence Alarm Acknowledge button must be pressed during the stage one del...

Страница 28: ...nly Inputs in the selected zone that are not configured as Water leak event type will not contribute to a Zonal Cause Effect Cause Effects can also be used to disable any Outputs or groups of Outputs...

Страница 29: ...ettings 18 1 Contrast Adjust The viewing angle contrast of the Hydrosense ID front panel display may be adjusted by turning the CONTRAST adjust potentiometer The contrast adjust potentiometer can be a...

Страница 30: ...250 mA in full alarm 19 4 Power Supply Supply Voltage 230 VAC nominal 10 15 Supply rating 3 Amps Battery Charger Charges up to 9 Ah sealed lead acid batteries with temperature compensation over the ra...

Страница 31: ...s start occurring from devices fitted at the other end of the loop Also excessive Loop Sounder Current will cause bad data faults to occur when the sounders are operated In general the user is unaware...

Отзывы: