INSTALLATION INSTRUCTIONS
Hydrosense ID Addressable Water Detection System
Document Part No. 3500039 Issue:01
Page | 23 of 32
16.1.6. Access Level Code Changes
The default codes to enter Access Level 2 and Access Level 3 can be changed via the Loop Explorer PC (LE2)
configuration utility only.
16.1.7. Panel Text
A forty-character message can be entered which is displayed when the control panel is in a quiescent condition.
This may be the company name and service contact telephone number or any other message agreed with the
end user.
16.1.8. Panel Modem Fitted
When selected, the panel expects a modem to be fitted to the PC port. The panel will poll the modem at 90-
second intervals and expect a response from the modem. If the modem does not respond, then a “Disconnected
Modem” message will be shown on the panel display.
16.1.9. Graphics System
When this is selected, event cleared messages will be sent to the PC port and printer port. This allows a graphics
system to track and automatically clear events, provided this facility is supported by the graphics system. This is
deselected by default, to reduce printer paper consumption. When selected, event cleared messages will be
printed after each event or activation has been reset.
16.1.10. – Zone Indicators
This option should always be set to 16 to match the zone LED’s on the panel.
16.1.11. – Display Invert
This option is used to change the LCD status display format. By default, black lettering is shown on a green
background.
Selecting this option will change the display to green lettering on a black background. This is useful in reducing
the brightness of the display when the panel is installed in darkened locations, such as control rooms and ships
bridges.
16.1.12. – Any 2 Devices to Bypass Delays – Def Ring Mode Outputs Only
When this option is set, any delayed outputs configured to respond to the “Default Ring Mode” pattern will
operate immediately upon the activation of any second Water Leak signal.
16.1.13. – Resound for Water Leak in Same Zone
When a Water Leak occurs in a zone and the sounders have been silenced, by default the sounders will not
activate when a second detector in the same zone goes to “Leak Detected”.
Selecting this option will cause the silenced sounders to activate from a second detection device in the same
zone.
16.1.14. – Resound for Leak Detection in Other Zone
When a Water Leak occurs in a zone and the sounders have been silenced, by default the sounders re-sound
when new Water Leak event is reported from a different zone.
Deselecting this configuration option will stop the silenced sounders from activating on the new zone Water Leak
event.
16.1.15. – Hide Disablement Event for Active Delays
This option applies to historical “V5.xx firmware” control panels only. As the Water Leak detection system is
currently on V6.xx this option should not be used.
16.1.16. – Delays Active on Initialisation
This option will switch delays On by default when the panel is restarted or powered on. It is recommended that
this option be selected on any system where delayed outputs are configured.
16.1.17. – Ignore Global C&E Disablement
Function not applicable – Currently this feature is not used.
16.1.18. Day/Night Times
Day night change times can be set for each day of the week by selecting the “Times” tab on the panel settings
screen.
Currently this feature is not used.