24
SW24.W
STAT
Diagnostics and reporting
Sub
menu
Description
Msg
display
ALM
Alarm log reading
Most recent alarm
0
Oldest alarm
10
ALMA
Error signalling (default = 1)
Only on display
1
On display and maintenance
output
2
MNPC
Reading of number of manoeu-
vres since last maintenance"
First 3 digits of the number of ma-
noeuvres since last maintenance
23
Last 3 digits of the number of ma-
noeuvres since last maintenance
256
In the case described above, the gate has
carried out 23,256 manoeuvres since the last
maintenance
MNPS
Number of manoeuvres since
last maintenance
Number of manoeuvres generating
a maintenance signal (in thou-
sands of manoeuvres)
(default
= OFF)
Maintenance signalling off
OFF
1,000 manoeuvres (minimum
interval)
1
300,000 manoeuvres (maximum
interval)
300
MNPA
Maintenance signalling (default
= 1)
Signalling only on display
1
Signalling on display and mainte-
nance output (MAN)
2
Signalling on display and flashing
light (rapid flashing at end of
manoeuvre)
3
Signalling on display, flashing light
(rapid flashing at end of mano-
euvre) and maintenance output
(MAN)
4
MNPE
Reset manoeuvres since last
maintenance counter
Waiting press OK for 5 s to reset
the counter to 0
oooo
MNTC
Total manoeuvres counter
First 4 digits of the number of ma-
noeuvres since last maintenance
12
Last 4 digits of the number of ma-
noeuvres since last maintenance
5874
In the case described above, the gate has
carried out 125,874 manoeuvres in total
LIFE
Life counter (days of activity of
the control panel)
Reading of the number of days of
activity of the control panel
584
In the case described above, the control
panel was active for 584 days
STAT
PONC
Number of control panel pow-
er-ups counter
Reading of the number of control
panel power-ups
2547
In the example shown above, the control
panel was powered up 2547 times (it could
indicate a poor quality mains electricity, with
frequent power cuts)
PONE
Reset number of control panel
power-ups counter
Waiting press OK for 5 s to reset
the counter to 0
oooo
RSTC
Number of self-reset counter
Reading of the number of control
panel self-resets
1123
A self-reset is a reset of the microswitch by
the control panel for safety reasons.
Typically the control panel goes to self-reset
when the minimum microswitch voltage
threshold has been reached. An excessive
number of self-resets could indicate a poor
quality power supply, subject to strong volt-
age fluctuation.
RSTE
Reset number of self-reset
counter
Waiting press OK for 5 s to reset
the counter to 0
oooo
TL
Installer telephone settings and
display
Press OK briefly to view the saved
number (use buttons ▲▼ to scroll)
First 4 digits of the installer number 3334
Next 4 digits of the installer
number
2548
Last 2 digits of the installer number
32
In the example shown above the installer
telephone number is: 333 4254832
Press OK for 5 s to enter the number edit
mode. Use buttons ▲▼ to change the value,
use OK to confirm the digit
INF
Control panel info display
Control panel name
SL24.W
Control panel firmware version
1.13
EXP
Connection module
Sub
menu
Description
Values
(default)
CNX1
Connection module on CNX1
connector
(1)
No module connected
OFF
Wi-Fi module EMC.W connected
1
EN