29
Appendix
Specification
(cont.)
Rated output
kW
700
780
860
950 1080
Product ID
H
acc. to Gas Device Directive
*1
CEĆ0085
H
acc. to Pressure Device Directive
*2
CEĆ0036
Flue gas resistance
Pa
mbar
280
2.8
390
3.9
490
4.9
450
4.5
580
5.8
Required draught
Pa/mbar
0
0
0
0
0
Flue gas characteristics
Temperature
*3
at
H
Boiler water temp. 60Ă
º
C
Ĉ at rated output
Ĉ at partial load
H
Boiler water temp. 80Ă
º
C
º
C
º
C
º
C
180
130
190
180
130
190
180
130
190
180
130
190
180
130
190
Product characteristics
(acc. to EnEV)
Efficiency
h
at
H
100 % of rated output
H
ă30 % of rated output
%
%
92.5
96.5
92.3
96.3
92.5
96.5
92.4
96.5
92.3
96.4
Relative standby loss q
B,70
%
0.17 0.16 0.14 0.13 0.13
Power consumption
*4
at
H
100 % of rated output
H
ă30 % of rated output
W
W
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
ĈĈ
*1
For operation with a safety temperature of 110
Ăº
C.
*2
For operation with a safety temperature of 120
Ăº
C.
*3
Flue gas temperatures measured as gross values at 20
Ăº
C combustion air temperature.
*4
Standard characteristic.
5692Ă517ĂGB
Содержание Vitorond 200 VD2 1080
Страница 30: ...34 5692 517 GB...
Страница 31: ...35 5692 517 GB...