27
Appendix
Water quality requirements
(cont.)
low salt content
with salt
content
Ele. conductivity at 25Ă
º
C
m
S/cm
10 to 30 >Ă30 to 100 >Ă100 to 1500
General requirements
clear, without sediments
pH value at 25Ă
º
C
Oxygen (O
2
)
alkaline earths (Ca + Mg)
Phosphate (PO
4
)
*1
When using oxygen
binders:
Sodium sulphite
(Na
2
SO
3
)
*5
mg/litre
mmol/litre
mg/litre
mg/litre
9
Ă
Ć
Ă
10
*1
<Ă0.1
*2
<Ă0.02
<Ă5
*4
ććććć
9
Ă
Ć
Ă
10.5
*1
<Ă0.05
*2
<Ă0.02
<Ă10
*4
ććććć
9
Ă
Ć
Ă
10.5
*1
<Ă0.02
*2,Ă*3
<Ă0.02
<Ă15
<Ă10
*1
If the regulations of the Drinking Water Order/Drinking Water Treatment Order are to
be maintained, then the pH value 9.5 and the PO
4
concentration of 7Ămg/litre should
not be exceeded.
*2
Generally, much lower values result from continuous operation.
*3
If suitable non-organic corrosion inhibitors are used, the oxygen concentration in the
re-circulated water may increase up to 0.1Ămg/litre.
*4
For heating water generators with smoke tube heat exchangers, e.g. flame
tube/smoke tube boilers, half the stated maximum level of phosphate concentration
of 2.5 or 5Ămg/litre PO
4
must be maintained as lower limit.
*5
Other suitable products may also be used. Please observe the respective guidelines
issued by the relevant supplier.
Conversion: 1Ămol/m
3
Ă=Ă5.6Ă
º
dH; 1Ă
º
dHĂ=Ă0.1792Ămol/m
3
; 1Ămval/kgĂ=Ă2.8Ă
º
dH
The VdTÜV datasheetĂ1466 advises
that other oxygen binders are
offered as chemical additives, which
may contain the following active
agents:
H
Ascorbic acid
H
Carbohydracide
H
Diethyl-hydroxylamine (DEHA)
H
Hydroquinone
H
Methyl ethyl ketone (MEk)
H
Tannins
These must be used with care
however, as they can give rise to
oxidation, cleavage and transformation
products under boiler operating
conditions.
Please refer to the above guidelines
for further information.