48
Interval
Activities
See page System user
Heating contrac-
tors
After 4000 to 6000 hours run
*2
Check combustion grate limit position
X
Service the safety valves and check their
operation
X
Check gaskets
X
Clean flue system and check it is working
correctly
X
Emissions testing
X
Every 3 years
Lubricate the drive chains and drive unit
bearings
X
Every 5 years
Replace the battery inside the control unit
X
After maintenance has been carried out
Maintenance confirmation and reset (con-
trol unit)
X
Note
The cleaning intervals are intended as a guide that can
be adapted, if required, to the fuel quality and operat-
ing conditions.
Maintenance and cleaning work on the fuel discharge system
Interval
Activities
See page
System user
Heating contrac-
tors
Fuel discharge system maintenance:
Fuel discharge system installation
and service instructions
X
Maintenance and cleaning work on the fuel store
Interval
Activities
See page
System user
Heating contrac-
tors
After 2 or 3 deliveries
Clean pellet storage room
X
After 2 years
Clean pellet storage room
X
*2
6000 hours when operating with pellets, 4000 to 6000 hours when operating with woodchips, interval subject to fuel quality.
Maintenance
Overview of maintenance and cleaning work
(cont.)
5679252