Vitoligno 300-C Installation/Service
5790 980 - 04
88
Coding in the factory set condition
Possible change
Solar
Differential DHW
6E:10
Differential temperature of
10 K between solar and
DHW heating to start DHW
heating by the solar thermal
system
6E:1
to
6E:50
Setting range of differential
temperature in K
Maximum temperature DHW
6F:70
Max. DHW temperature limit
when heated by the solar
thermal system. DHW
is heated by the solar thermal
system up to this temperature.
If DHW is heated by a combi
tank, this temperature refers
to the first buffer tank
temperature sensor.
6F:0
to
6F:100
Setting range in °C
Differential buffer
70:20
Differential temperature of
20K between solar and
heating water buffer tank to
start heating water buffer
tank by the solar thermal
system
70:1
to
70:50
Setting range in °C
Additional function, solar
71:0
Additional function of tank
heating by the solar thermal
system disabled. Code only
available when DHW heating
is connected to the boiler.
71:0
to
71:23
Start time of the solar additional
function. Solar auxiliary function:
Signal for starting the transfer pump
of the solar thermal system. This also
heats the lower area of the DHW tank to
the required temperature.
Time adjustable from 1:00 am (01:00 h)
(“71:1”) to 11:00 pm (23:00 h)
(“71:23”). The time of the function must
be between the enable times for DHW
heating.
Additional function runtime
72:0
Circulation pump off.
72:0
to
72:180
Runtime of solar de-stratification pump in
min, adjustable from 1 min to 180 min.
Only available with code “71:1 - 23”.
Coding
Coding 1
(continued)