Vitoligno 300-C Installation/Service
5790 980 - 04
72
Commissioning, Inspection and Maintenance
Vitoligno 300-C
System user
Heating contractor
After 6,600 to 8,800 lb. (3,000 to 4,000 kg) of pellets consumed or
at least once per year
Empty ash box (see page 71).
X
--
Check the system pressure. Minimum system pressure: 14.5 psi (1.0 bar)
X
--
After 33,000 lb. (15,000 kg) of pellets consumed or at least once per year
Check all installed position switches
--
X
Remove the flue ash from the chimney
--
X
Clean the flue pipe
--
X
Clean the secondary heating surfaces
--
X
Clean the flue gas collector chamber
--
X
Clean the Lambda probe with a soft brush
--
X
Clean the flue gas temperature sensor
--
X
Clean flue gas fan
--
X
Clean the combustion chamber
--
X
Clean the reversing chamber
--
X
Clean the finned grate
--
X
Clean the ignition element and ignition pipe
--
X
Clean the ash chamber and ash removal parts
--
X
Clean the pellet sensor in the pellet hopper with a soft brush
--
X
Clean the intake grille in the pellet hopper with a vacuum cleaner
--
X
Clean the vacuum module with a vacuum cleaner
--
X
Check all gaskets on the covers and replace if necessary
--
X
After 66,000 lb. (30,000 kg) of pellets consumed or at least once every 3 years
Maintenance of moving parts (drive chains, shafts, friction bearings, cogs, etc.)
--
X
Every 5 years
Replace the battery inside the control unit.
--
X
Have a heating contractor clean the interior of the
boiler once a year.
WARNING
Hot surfaces can lead to serious injuries.
Only open the boiler after it has cooled down.
CAUTION
During maintenance and cleaning work, and when
manipulating the ash box, there is a risk of fire and
burns due to hot parts and ash.
Wear suitable safety gloves.
Only dispose of the hot ash in fireproof containers
with covers.
Overview of Maintenance and Cleaning Work in the Boiler
WARNING
Breathing in ash or pellet dust is detrimental to health.
Wear a (Noish N95) dust mask to protect your
respiratory tract.