81
5790 980 - 04
Vitoligno 300-C Installation/Service
Coding
Coding 1
(continued)
Coding in the factory set condition
Possible change
Boiler
(continued)
Flue gas fan start speed
3C:...
Speed of the flue gas fan
when the boiler starts
(heat-up) in %
3C:...
to
3C:...
Setting range in %
Flue gas fan minimum speed
3D:...
Min. speed of the flue gas
fan in %
3D:...
to
3D:...
Setting range in %
Flue gas fan maximum speed
3E:...
Max. speed of the flue gas
fan in %
3E:...
to
3E:...
Setting range in %
External demand
44:0
No external boiler demand
(digital) is connected.
44:1
An external boiler demand (digital) is
connected.
Default output
45:0
No external default output
(0 - 10V) of the boiler is
connected.
45:1
An external default output (0 - 10V)
of the boiler is connected.
Feed runtime, boiler ignite, recharge
4D:...
Max. runtime of feed screw
conveyor on ignition
4D:...
to
4D:...
Setting range in sec.
Min. runtime boiler run-on
8C:...
Min. runtime boiler run-on
8C:...
to
8C:...
Setting range in min.
Charging
Is available if code “Charging scheme”, hardware group, is set.
Feed screw conveyor heat-up cycle
14:...
Start cycle of the feed
screw conveyor in % after
boiler ignition
14:...
to
14:...
Setting range in %
Feed screw conveyor maximum cycle
15:...
Max. cycle limit of feed
screw conveyor in %
15:...
to
15:...
Setting range in %
Day hopper idle runtime (man. charging)
27:30
30 minutes rotary lock
valve idle runtime with
manual charging of the
boiler.
Code is only available with
manual charging of the
boiler.
27:1
to
27:100
Setting range in min