6 Routine Servicing
a)
Check at the siphon, that the condensate can drain freely.
b)
Remove the retaining clip and the siphon.
c)
Clean the siphon.
d)
Fill the siphon with water, fit it to the boiler and secure with the retaining clip.
6.6 Checking the Condensate Drain and Cleaning the Siphon
6.7 Domestic Hot Water Flow Limiter (Combi Boiler only)
a)
Shut of the cold water supply.
b)
Release the Allen screws (A).
c)
Remove the flow switch (B) and remove the flow limiter (C) downwards.
d)
Check the flow limiter (C) and replace if excessive deposits are evident or if
the unit appears damaged. Replace and secure flow switch (B)
48