Error
System
Cause of fault
Action
Message
Behaviour
30
Boiler cools down
Boiler temperature sensor
Check boiler temperature sensor
shorted out
38
Boiler cools down
Boiler temperature sensor
Check boiler temperature sensor
open circuit
b0
Boiler cools down
Flue gas temperature
Check flue gas temperature sensor
sensor shorted out
b8
Boiler cools down
Flue gas temperature
Check flue gas temperature sensor
sensor open circuit
b7
Boiler will not run
Boiler coding card missing or
Check boiler coding card
incorrect card fitted
E4
Boiler will not run
Supply voltage fault
Replace control unit
E5
Boiler will not run
Flame detection fault
Check ionisation electrode. Check
flue gas system for leaks. PRESS
E6
Burner fault
Flue gas/air supply blocked
Check flue gas/air supply Check air
pressure switch & cables PRESS
F0
Burner will not run
Internal fault
Replace controls unit
F1
Burner will not run
Flue gas temperature limiter
Check heating system water level.
has locked out
Vent heating system PRESS after
20 minutes
F2
Burner will not run
Flow temperature limiter
Check heating system water level.
has responded
Check circulation. Check limit
thermostat and leads. PRESS
F3
Burner will not start
False flame signal
Check ionisation electrodes and
leads. PRESS
F4
Burner will not run
No flame signal
Check ionisation electrode, gas
pressure, gas valve, ignition
transformer/electrode and
condensate drain. PRESS
F7
Burner locked out
Differential pressure sensor faulty
Check differential pressure sensor
F8
Burner will not run
Gas valve closes too late
Check gas valve. PRESS
F9
Burner will not run
Fan speed too low at burner start
Check fan, fan cables, supply and
fan control PRESS
A
Burner will not run
Fan does not stop
Check fan, fan cables and fan
control. PRESS
Fd
Burner at lockout
Burner control unit fault
Check ignition electrodes/leads. Check
for EMC interference. PRESS
If fault persists replace control unit
FE
Burner at lockout
Strong EMC interference,
Remove EMC, Check coding card or
faulty boiler coding card
replace control unit
or main PCB faulty.
FF
Burner at lockout
Internal fault
Remove EMC, Check coding card or
replace control unit
8 Fault Finding
Diagnosis and correction. See the following table of error messages: