58
Rated heating output
TF/TR = 50/30
kW
29 - 75
29 - 87 38 - 115 47 - 142 37 - 186 62 - 246
62 - 311
TF/TR = 80/60
kW
26 - 69
26 - 80 35 - 105 43 - 130 34 - 170 56 - 225
57 - 285
Flue gas parameters
*2
Temperature
(at a return temperature of
30 °C)
■
At rated heating output
°C
45
45
45
45
45
45
45
■
At partial load
°C
35
35
35
35
35
35
35
Temperature
(at a return temperature of
60 °C)
■
At rated heating output
°C
75
75
75
75
75
75
75
Mass flow rate
(for natural
gas)
■
At rated heating output
kg/h
109
126
166
207
269
358
452
■
At partial load
kg/h
42
42
56
69
54
89
91
Mass flow rate (for LPG)
■
At rated heating output
kg/h
–
–
–
–
271
360
454
■
At partial load
kg/h
–
–
–
–
54
90
92
Flue gas connection
7
mm
160
160
160
160
200
200
200
Ventilation air connection
7
mm
160
160
160
160
160
160
160
Draught at the flue outlet
*3
Pa
70
70
70
70
70
70
70
mbar
0.7
0.7
0.7
0.7
0.7
0.7
0.7
Product parameters ac-
cording to EnEV
Standard seasonal efficien-
cy [to DIN]
For heating system tempera-
ture 40/30 °C
%
Up to 98 (Hs) [gross cv]
For heating system tempera-
ture 75/60 °C
%
Up to 96 (Hs) [gross cv]
Standby loss qB,70
%
0.6
0.6
0.5
0.4
0.4
0.3
0.3
MatriX burner
Rated boiler heating output
T
F
/T
R
50/30 °C
kW
75
87
115
142
186
246
311
MatriX radiant burner
MatriX cylinder burner
Rated heat input of the
burner, lower/upper out-
put
*4
(modulation)
kW
27/71
27/82
36/109
45/134
35/176
58/232
59/293
Burner type
CM2C
Product ID
See boiler
Voltage
V
230
230
230
230
230
230
230
Frequency
Hz
50
50
50
50
50
50
50
*2
Values for calculating the size of the flue system to EN 13384, based on 10 % CO
2
for natural gas
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
The details for partial load refer to the lower rated heating output. If the partial load differs (subject to burner operating
mode), calculate the flue gas mass flow rate accordingly.
*3
If the Vitocrossal 200 is used with moisture-resistant chimneys, the maximum draught is 0 Pa.
*4
Corresponds to the rated heat input of the boiler.
Specification
Specification
(cont.)
5831036