57
Rated heating output
TF/TR = 50/30
kW
29 - 75
29 - 87 38 - 115 47 - 142 37 - 186 62 - 246
62 - 311
TF/TR = 80/60
kW
26 - 69
26 - 80 35 - 105 43 - 130 34 - 170 56 - 225
57 - 285
Rated heat input
kW
71
82
109
134
176
232
293
Product ID
CE 0085CS0180
Permiss. operating temper-
ature
°C
95
95
95
95
95
95
95
Permiss. flow temperature
(= safety temperature)
°C
110
110
110
110
110
110
110
Max. permiss. operating
pressure
bar
6
6
6
6
6
6
6
MPa
0.6
0.6
0.6
0.6
0.6
0.6
0.6
Min. permiss. operating
pressure
bar
0.5
0.5
0.5
0.5
0.5
0.5
0.5
MPa
0.05
0.05
0.05
0.05
0.05
0.05
0.05
Test pressure
bar
7.8
7.8
7.8
7.8
7.8
7.8
7.8
MPa
0.78
0.78
0.78
0.78
0.78
0.78
0.78
Boiler body dimensions
Length
mm
1281
1281
1281
1281
1291
1291
1291
Width
mm
660
660
660
660
760
760
760
Height
mm
1178
1178
1178
1178
1277
1277
1277
Total dimensions
Length
mm
1774
1774
1774
1774
1793
1793
1793
Width
mm
810
810
810
810
910
910
910
Height
mm
1178
1178
1178
1178
1277
1277
1277
Foundation dimensions
Length
mm
1200
1200
1200
1200
1200
1200
1200
Width
mm
800
800
800
800
800
800
800
Height
mm
100
100
100
100
100
100
100
Weight
Total weight
■
Boiler incl. burner, thermal
insulation and boiler control
unit
kg
381
381
387
389
433
448
461
■
Handling weight (boiler
body)
kg
240
240
240
242
286
298
311
Water capacity
l
225
225
225
221
306
292
279
Connections
Boiler flow
PN 6 DN
50
50
50
50
65
65
65
Boiler return
PN 6 DN
50
50
50
50
65
65
65
Safety connection
PN 6 DN
50
50
50
50
50
50
50
Safety valve (male thread)
R
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Drain (male thread)
R
1
1
1
1
1
1
1
Trap with condensate drain
mm
20
20
20
20
20
20
20
Specification
Specification
5831036