15
Static pressure
Rated heating output 75 and 87 kW
A
Fig. 7
Rated heating output 115 to 311 kW
A
Fig. 8
1.
Close the gas shut-off valve.
2.
Undo the screw in test connector
A
, but do not
remove.
3.
Connect the pressure tester at test connector
A
.
4.
Open the gas shut-off valve.
5.
Check the static pressure.
6.
Record the actual value in the report (on
page 55).
Supply pressure
Note
See type plate for supply pressures for operation with
other country-specific gas types.
1.
Start the burner with emissions test mode enabled
(in control unit menu).
Commissioning, inspection, maintenance
Checking static pressure and supply pressure