60
Press the following keys:
1.
|
/
~
Number of wands of the changeover unit:
"2"
,
"3"
,
"4"
,
"5"
,
"6"
,
"7"
or
"8"
.
2.
d
to confirm.
Select shut-off gate valve
Press the following buttons:
1.
|
/
~
for shut-off gate valve
"Yes/No"
.
2.
d
to confirm.
Select extinguishing water tank
Press the following buttons:
1.
|
/
~
for extinguishing water tank
"Yes/No"
.
2.
d
to confirm.
Select sensor fill level, fuel store
To specify whether a level sensor is present in the fuel
store, press the following buttons:
1.
|
/
~
for pellet store sensor
"Yes/No"
.
2.
d
to confirm.
Set flue gas filter
Press the following buttons:
1.
|
/
~
"No"
if no flue gas filter is installed
or
"External"
for demand to flue gas filter and
fault message from flue gas filter via floating
contact
or
"Internal"
for control of flue gas filter via
CAN bus
2.
d
to confirm.
Selecting external digital input
Available if
"No"
was selected for the cascade.
Press the following buttons:
1.
|
/
~
for external demand with external digital
input
"No/demand/block"
.
2.
d
to confirm.
Commissioning, inspection, maintenance
Commissioning the heating system
(cont.)
5679249