155
Fuel
Wood-
chips
Wood-
chips
Rated heating output
kW
50
60
Installed weights
Boiler
without
water or
■
Feed (without shut-off gate valve/rotary lock valve)
■
Ash box
■
Thermal insulation
kg
1077
1077
Boiler
with
water and
■
Feed (without shut-off gate valve/rotary lock valve)
■
Ash box
■
Thermal insulation
kg
1287
1287
Capacity
Boiler water
l
210
210
Ash box
l
45
45
kg
18
18
Protection class
I
I
IP rating to EN 60529; ensure through design/installation.
IP 20
IP 20
Type of operation to EN 60730-1
Type 1 B
Type 1 B
Operation of the boiler
Non-con-
densing
Non-con-
densing
Permiss. ambient temperature
■
During operation
(Use in boiler rooms, standard ambient conditions)
°C
0 to +35
0 to +35
■
During storage and transport
°C
−
20 to +65
−
20 to +65
Electrical data
■
Rated voltage
V
∼
400
400
■
Rated frequency
Hz
50
50
■
Max. rated current
A
∼
10
10
Power consumption
Ignition
W
1400
1400
Ash removal
W
25
25
Feed
W
380
380
Flue gas fan
W
100
100
Grate drive
W
14
14
Heat exchanger cleaning
W
14
14
■
Boiler at Q
N
W
234
259
■
Boiler at Q
min
W
122
122
■
Boiler on standby
W
26
26
Rated relay output breaking capacity at 230 V
∼
Heating circuit pumps
A
∼
4 (2)
4 (2)
Circulation pump for cylinder heating
A
∼
4 (2)
4 (2)
Solar circuit pump, as alternative to heating circuit pump M2
A
∼
4 (2)
4 (2)
DHW circulation pump
A
∼
4 (2)
4 (2)
Central fault message
A
∼
4 (2)
4 (2)
Mixer motor
A
∼
0.2 (0.1)
0.2 (0.1)
Discharge motor, room discharge/silo, mole
W
Max. 200
Max. 200
Specification
Specification
(cont.)
5679249
Appendix