11
5285 429 - 03
Vitorond 200, VD2 Series 320 to 1080 Installation
Set-up
Boiler Set-up and Location
Boiler
model
VD2-
320
VD2-
380
VD2-
440
VD2-
500
VD2-
560
VD2-
630
VD2-
700
VD2-
780
VD2-
860
VD2-
950
VD2-
1080
a
in. (mm)
45
(1140)
49
c
(1265)
54
c
(1390)
59
c
(1515)
64
b
(1640)
69
b
(1765)
74
b
(1890)
79
a
(2015)
84
a
(2140)
87
(2205)
94
(2390)
b
in. (mm)
52
a
(1330)
57
a
(1455)
62
a
(1580)
67
(1705)
72
(1830)
77
(1955)
82
(2080)
86
c
(2205)
91
c
(2330)
96
b
(2460)
101
b
(2580)
The boiler must be installed on a levelled base or
foundation, which must be designed to carry the entire
weight of the boiler, water fill, burner and attached
piping. To ease the installation of the individual sections,
angle-iron or flat steel may be incorporated into the
concrete foundation. Surface width of steel strips should
be 4 in. (100 mm).
Boiler Base
>=4 in. (100 mm)
35
b
in. (900 mm)
43
a
in. (1100 mm)
2 in. (50 mm)
4 in.
(100 mm)
4 in.
(100 mm)
5
b
in.
(140 mm)
a
b
Note:
Inch dimensions rounded to the nearest ¼ in.