Appendix
16
Technical Data
(continued)
Liquid propane
Burner Model
Boiler
P200
VB2-18
P200
VB2-22
P200
VB2-33
P200
VB2-40
P400
VB2-50
P400
VB2-63
Input
MBH
kW
90
26
116
34
146
42
185
54
238
69
300
88
Flow Rate
ft
3
/h
m
3
/h
36
1.02
46.4
1.31
58.4
1.65
74
2.10
95.2
2.70
120
3.40
Gas Valve
Model
MVD-LE 205/6
MVD-LE 205/6
MVD-LE 205/6
MVD-LE 205/6
MVD-LE 207/6
MVD-LE 207/6
Manifold
Press.
“w.c.
1.2
1.4
1.6
2.4
1.3
1.7
T in seconds
1 ft
3
0.01 m
3
100
35.31
77.58
27.40
61.64
21.76
48.62
17.17
37.80
13.35
30.00
10.59
Combustion
Head Setting
0.5
2.0
3.0
3.5
1.0
5.0
Air Gate
Setting
2.0
2.0
2.75
3.75
2.4
2.8
The above specifications are for 0-2000 ft. above sea level.
Burner test results
The indicated values for manifold and
air gate settings are the result of
production line testing under ideal
conditions.
Final burner adjustment to suit local
field conditions is necessary for safe
operation.
Observe the stated minimum and
maximum supply gas pressures.
Exposing the burner gas train to supply
pressures other than the stated values
can cause unsafe conditions.
Viessmann strongly recommends the
installation of an approved type CO
detector in the vicinity of any gas
burning equipment. Observe national
and/or local code requirements. If in
doubt consult your local LP company.
Verification of results
The burner adjustment values indicated
serve as a starting point only.
Combustion results must be field
verified using properly calibrated
Bacharach or equivalent instruments.
Each burner is certified for one input
only. Do
not
overfire or underfire
burner.
Technical data
Fuel
propane gas
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Average
heating value
2500 MBH/ft
3
. . . . . . . . . . . . . . . . . . .
Specifications
Inlet gas pressure
min. 8” w.c.
. . . . . . . . . . .
max. 13” w.c.
Draft regulator
VB2-18 to -40
MG1 6”
. . . . . . . . . . . . . . .
VB2-50 to -63
MG1 7”
. . . . . . . . . . . . . . .
Overfire draft
+0.01” w.c.
. . . . . . . . . . . . . . . . . . .
Max. breeching draft
-0.02” w.c.
. . . . .
INPUT = 3600/T x 2500
where
T
= TIME (sec.) for 1 ft
3
propane gas
INPUT = (3600 x 0.01 x 2500 x 35.31)/T
where
T
= TIME (sec.) for 0.01 m
3
propane
gas
5
2
6
5
6
6
5
v
2
.5
Do not overfire or underfire burner.
Factory settings to be verified or
changed by qualified heating
contractor, depending on field
measured combustion results.
CAUTION
The burner settings above do not
guarantee safe operation. Burner
settings serve to help provide smooth
operation at initial start-up.
CAUTION
IMPORTANT