31
Specification
Boiler water tem-
perature sensor
Buffer tempera-
ture sensor
Flow temperature
sensor
Return tempera-
ture sensor
Flue gas tempera-
ture sensor
Outside tempera-
ture sensor
Sensor type
Pt1000
Pt1000
Pt1000
For heating circuit and DHW
heating sensors, refer to chapter
"Extension kit".
Lambda probe
For capturing the residual oxygen con-
tent in the flue gas.
Checking the Lambda probe
1.
Remove Lambda probe from flue out-
let.
2.
Check the Lambda probe for possible
contamination and/or damage.
3.
Check the connecting cable for pos-
sible damage.
Notes
■ Never paint, wax or treat the probe
with any other substance. Only use
special grease suitable for Lambda
probes to lubricate the threads.
■ Never solder the connecting cable; it
may only be crimped, clamped or
secured with screws.
Connection
The oxygen is connected with plug
a:K
(see chapter "Connection and wiring dia-
gram", page 42).
Calibrating the Lambda probe
1.
Cleaning the Lambda probe
2.
Hang the probe for at least 15
minutes outside the induced draught
casing in the installation room.
3.
Call up the Service menu at the con-
trol unit
4.
Select
(
menu point
"Boiler"
. Con-
firm with OK.
5.
Select
(
menu point
"O2 sensor
balance"
[calibrate O2 probe]. Con-
firm with OK.
Troubleshooting
Repair
(cont.)
5604 447 GB
Содержание KOB Pyromat ECO
Страница 42: ...42 230V connection Designs Connection and wiring diagram 5604 447 GB ...
Страница 43: ...43 LV connection Designs Connection and wiring diagram cont 5604 447 GB ...
Страница 46: ...46 Plug X1 Drawing assignment 1 6 1 2 3 4 5 6 7 X1 Designs 230 V plug cont 5604 447 GB ...
Страница 57: ...57 030 022 021 020 025 031 031 012 019 025 044 024 024 035 Parts lists Parts lists cont 5604 447 GB ...
Страница 58: ...58 008 004 001 002 032 043 037 038 007 007 007 009 002 005 Parts lists Parts lists cont 5604 447 GB ...
Страница 59: ...59 006 006 006 007 034 036 013 015 018 014 016 033 017 015 003 Parts lists Parts lists cont 5604 447 GB ...