10
0.2
Outside temperature in °C
Boiler water or Flow temperature in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0
-10
-20
10
A
B
2.0
2.2
Set room temperature in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30
1.8
1.6
C
-14
Example for outside temperature
−
14 °C
:
A
Underfloor heating system, slope
0.2 to 0.8
B
Low temperature heating system,
slope 0.8 to 1.6
C
Heating system with a boiler water
temperature in excess of 75 °C,
slope 1.6 to 2.0
Adjusting the set room temperature
Individually adjustable for each heating
circuit.
The heating curve is offset along the axis
of the set room temperature. When the
heating circuit pump logic function has
been enabled, it modifies the starting
and stopping characteristics of the heat-
ing circuit pump.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5604 447 GB
Содержание KOB Pyromat ECO
Страница 42: ...42 230V connection Designs Connection and wiring diagram 5604 447 GB ...
Страница 43: ...43 LV connection Designs Connection and wiring diagram cont 5604 447 GB ...
Страница 46: ...46 Plug X1 Drawing assignment 1 6 1 2 3 4 5 6 7 X1 Designs 230 V plug cont 5604 447 GB ...
Страница 57: ...57 030 022 021 020 025 031 031 012 019 025 044 024 024 035 Parts lists Parts lists cont 5604 447 GB ...
Страница 58: ...58 008 004 001 002 032 043 037 038 007 007 007 009 002 005 Parts lists Parts lists cont 5604 447 GB ...
Страница 59: ...59 006 006 006 007 034 036 013 015 018 014 016 033 017 015 003 Parts lists Parts lists cont 5604 447 GB ...