1.
Route flexible flue
3
through duct cover
9
.
2.
Position the lower part of duct cover
9
onto the duct and secure it there.
3.
Position metal supporting ring
10
on the
lower part of duct cover
9
.
4.
Push threaded ring
11
as far as possible
onto flexible flue
3
.
5.
Trim flue
3
flush with the top of
threading ring
11
.
6.
Screw terminal pipe
12
onto threading
ring
11
.
7.
Invert weather hod
13
over terminal
piece
12
and click into place.
8.
Hook safety rope
14
into the drilled holes
of duct cover
9
.
Connection to a moisture-resistant chimney
Routing through a duct
(cont.)
Condensing boilers can be connected to
moisture-resistant chimneys to EN 13384-
1, if the chimney manufacturer has verified
their suitability on the basis of the specified
flue gas values.
For this, local conditions (e.g. heating water
return temperature, connecting pipe design,
etc) must be taken into consideration.
As transition from the flue to the MR
chimney, use a plug-in adaptor, such as that
offered by Schiedel or an adaptor by Plewa.
21
5458 035 GB