1.
Create a wall outlet (min. diameter):
n
105 mm (system size 60)
n
130 mm (system size 80)
n
160 mm (system size 100).
2.
Push external wall bend
8
with wall bezel
5
from the outside into the hole in the
wall.
3.
Fit air intake
9
as near as possible to
external wall bend
8
.
4.
Secure the wall bezel from the inside.
5.
Connect the balanced flue inter-
connecting pipe from the inside and route
with a slope of at least 3° (approx. 50
mm/m) towards the boiler.
6.
Fit sections with external wall clips at a
constant distance from the external wall.
Set external wall clips at centres of
up to 1 m.
7.
Please note
Ensure the specified minimum
lengths above the roof are
observed. Never trim roof outlets
outside the roof.
n
Use universal tiles or air vent
tiles with pipe outlets.
n
Set balanced flue sliding coupling
3
below the roof outlet.
n
Install pipe outlets for Klöber or
universal roof tiles in accordance
with manufacturer’s details.
n
Position the roof outlet
from the top onto tiles.
n
Connect the external
wall line from below.
31
5458 035 GB
Routing over an external connection
(cont.)
Installation
!
Max. total flue length
up to the boiler flue connection (at system temperature 50/30°C)
Vitodens 100-W
Rated output range (kw)
9
11
11
26.0 30.0 35.0
max. length (m) - system size 60/100
20
15
15
Vitodens 200-W
Rated output range
4.8 6.5 8.8
8.8 17.0 17.0 30.0 30.0
19.0 26.0 30.0 35.0 45.0 60.0 80.0 105.0
max. length (m) - system size 60/100
20
20
15
15
–
–
–
–
- system size 80/125
–
–
–
–
20
15
–
–
- system size 100/150
–
–
–
–
–
–
20
20
Vitodens 222-F
Rated output range (kw)
4.8 6.5 8.8
8.8
19.0 26.0 30.0 35.0
max. length (m) - system size 60/100
20
20
15
15
Vitodens 242-F
Rated output range (kw)
4.8 6.5
19.0 26.0
max. length (m) - system size 60/100
20
20
Allowed for are 2 bends 87° (incl. support bends).