Vertical outlet for sloping or flat roofs
(cont.)
Roof construction according to the flat roof guideline
5458 035 GB
25
Max. total flue length
up to the boiler flue connection (at system temperature 50/30°C)
Vitodens 100-W
Rated output range (kw)
9
11
11
26.0 30.0 35.0
max. length (m) - system size 60/100
10
10
10
Vitodens 200-W
Rated output range
4.8 6.5 8.8
8.8 17.0 17.0 30.0 30.0
19.0 26.0 30.0 35.0 45.0 60.0 80.0 105.0
max. length (m) - system size 60/100
10
10
10
10
–
–
–
–
- system size 80/125
–
–
–
–
10
6
–
–
- system size 100/150
–
–
–
–
–
–
15
15
Vitodens 222-F
Rated output range (kw)
4.8 6.5 8.8
8.8
19.0 26.0 30.0 35.0
max. length (m) - system size 60/100
10
10
10
10
Vitodens 242-F
Rated output range (kw)
4.8 6.5
19.0 26.0
max. length (m) - system size 60/100
10
10
Allowed for are 2 bends 87° (incl. support bends).
A
Flat roof collar
B
Gravel ballast layer
C
Insulation membrane
D
Ventilation membrane
E
Thermal insulation
F
Insulation
G
Ceiling
H
Flue