141
Type BWC in conjunction with "conversion kit for water/
water heat pump"
351.A07
Refrigerant circuit
Refrigerant
R134a
Refrigerant charge
kg
2.35
Permiss. operating pressure, low pressure side
bar
21
MPa
2.1
Permiss. operating pressure, high pressure side
bar
25
MPa
2.5
Compressor
Type
Hermetically sealed
scroll
Oil in compressor
Type
Emkarate RL32
3MAF
Permiss. operating pressure
Primary circuit
bar
3
MPa
0.3
Secondary circuit
bar
3
MPa
0.3
Dimensions
Total length
mm
844
Total width
mm
600
Total height without programming unit
mm
962
Total height (programming unit pivoted up)
mm
1155
Weight
kg
146
Connections
Primary circuit flow/return
G
1½
Secondary circuit flow/return
G
1½
Sound power level
(tested with reference to
EN 12102/EN ISO 9614-2) Weighted total sound pow-
er level at W10
±3
K/W35
±5 K
■ At rated heating output
dB(A)
44
Specification
Specification
(cont.)
5546 273 GB
Service
Содержание BW 351.A07
Страница 28: ...28 Removing the top panel 1 Installation sequence Siting the heat pump cont 5546 273 GB ...
Страница 88: ...88 Opening the casing door Troubleshooting Repairs cont 5546 273 GB ...
Страница 90: ...90 D C Q R S V K X P F J U T X Q S T R D Y W Type BWC 351 A07 Troubleshooting Repairs cont 5546 273 GB ...