59
Compressor power supply (400 V~)
L1
400 V/50 Hz
?
L2
L3
N
PE
3/N/PE
L1
L2
L3
N
■ For MCB/fuse protection subject to the
compressor rating, see specification.
■ Economy tariff and power-OFF can be
applied.
■ No parameters need to be set when
applying economy tariffs with power-
OFF facility. The compressor is shut
down during the power-OFF time.
■ Recommended power cable:
5 x 2.5 mm
2
Max. cable length:
50 m
Power supply with power-OFF
Power-OFF without on-site load disconnection
The power-OFF signal is connected
directly to the heat pump control unit.
When power-OFF is enabled, the com-
pressor is "forced" off, and in the 2-stage
version (type BW + BWS),
both
com-
pressors are switched off.
Parameter
"Output for instant. heating
water heater at power-OFF 790A"
determines whether and at what stage
an instantaneous heating water heater (if
installed) remains operational during
power-OFF.
Service instructions for
"Vitotronic 200 heat pump control
unit"
Note
Observe the technical connection condi-
tions of the relevant power supply util-
ity.
Installation sequence
Power supply
(cont.)
5546 273 GB
Installation