82
Solar
Parameters for solar thermal system in con-
junction with solar control module, type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
"Solar"
Ó
Parameter C0xx
See installation and service in-
structions for "solar control mod-
ule, type SM1".
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"0"
No cooling
"1"
Natural cooling with NC-Box
without mixer (accessory)
"2"
Natural cooling with NC-Box
with mixer (accessory)
"3"
"Active cooling"
"Cooling"
Ó
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Separate cooling circuit SKK
Ice store/solar air absorber
Parameters for ice store and solar air absorb-
er
Setting
"System definition"
Ó
"Select primary source 7030"
"1"
"System definition"
Ó
"External extension 7010"
"2"
"Solar"
Ó
"Type solar control unit 7A00"
"2"
"System definition"
Ó
■
"Start hysteresis solar air absorber 7031"
"0"
to
"500"
(
≙
0 to 50 K)
■
"Min. runtime to suppress summer mode
7035"
"0"
to
"1440"
min
■
"Last calendar week for summer mode 7036"
Calendar week
"1"
to
"53"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5546 273 GB
Содержание BW 351.A07
Страница 28: ...28 Removing the top panel 1 Installation sequence Siting the heat pump cont 5546 273 GB ...
Страница 88: ...88 Opening the casing door Troubleshooting Repairs cont 5546 273 GB ...
Страница 90: ...90 D C Q R S V K X P F J U T X Q S T R D Y W Type BWC 351 A07 Troubleshooting Repairs cont 5546 273 GB ...